SECTION 6
PREVENTATIVE MAINTENANCE
WARNING
The terminals of the PV input may be energized if the arrays are energized. In addition, allow 5 minutes for all capacitors within the enclosure to discharge af- ter shutting down the
1.Turn the on/off switch to the off position.
2.Open the PV array disconnect switch (if present).
3.Open the AC disconnect (if present).
4.Open the isolation transformer circuit breaker.
5.Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.
TURN-ON PROCEDURE
Refer to Section 3 for a detailed
1.Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect switch.
2.Close the isolation transformer circuit breaker.
3.Close the AC disconnect (if present).
4.Close the PV array disconnect switch (if present).
5.Turn the on/off switch to the on position.
After a 15 second initialization period and a 5 minute wake up period, the