Xantrex Technology PV-30208 Section Preventative Maintenance, TURN-ON Procedure

Page 31

SECTION 6

PREVENTATIVE MAINTENANCE

WARNING

The terminals of the PV input may be energized if the arrays are energized. In addition, allow 5 minutes for all capacitors within the enclosure to discharge af- ter shutting down the PV-30208.

1.Turn the on/off switch to the off position.

2.Open the PV array disconnect switch (if present).

3.Open the AC disconnect (if present).

4.Open the isolation transformer circuit breaker.

5.Install lockout devices on the isolation transformer circuit breaker and PV disconnect switch.

TURN-ON PROCEDURE

Refer to Section 3 for a detailed first-time turn on procedure.

1.Remove any lockout devices from the isolation transformer circuit breaker and PV disconnect switch.

2.Close the isolation transformer circuit breaker.

3.Close the AC disconnect (if present).

4.Close the PV array disconnect switch (if present).

5.Turn the on/off switch to the on position.

After a 15 second initialization period and a 5 minute wake up period, the PV-30208 will automatically begin power tracking, given the PV voltage is greater than the PV start voltage setpoint.

DOCUMENT: 151315

PV-30208 Photovoltaic Inverter

6-2

Operation and Maintenance Manual

 

 

Copyright 2003, Xantrex Technology Inc.

Image 31
Contents Copyright 2003, Xantrex Technology Inc South Vasco RoadTable of Contents Major Components Section Product Description IntroductionMain Enclosure Solar Control Unit SCU Section Product DescriptionInterconnection Standards Compliance Matrix Bus BoardEquipment Symbol Section Product Description SpecificationsEnclosure Front Access Panel Section Safety Safety FeaturesPV Ground Fault Detection Anti Island Protection Section Safety Isolation ProcedureUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsFloor Mounted Section Installation and Initial TURN-ONInstallation Instructions InstallationSection Installation and Initial TURN-ON Phase-Sequencing Ground Fault DetectionArray Grounding Section Installation and Initial TURN-ON Frame Optional PV Conductor PV Array Ground Jumper Wiring Diagram Optional BoxPV-30208 Inverter Visual Inspection, PV-30208 Visual Inspection, PV Array WiringInitial Power Visual Inspection, Isolation Transformer WYE/WYESystem Verification Fine TuningOverview Section Operation Description of System OperationOperating States Section Operation Operation Features Section Operation Diagram Of Monopolar ConfigurationBlock Automatic Wake Up PV Voltage Optimization Peak Power TrackingCurrent Imbalance Detection DC Overvoltage DetectionSection Operation Operator Interface Example of Normal System Operation System Fault System Sleep Test System Stop System ShutdownSection Operation System Operating Parameters User Factory Password Parameter Description Section Operation Fault Conditions Section Troubleshooting GeneralIPM Device Fault 0x0001 Through Fault DescriptionsAC Line Under Frequency Fault Section TroubleshootingAC Line Voltage Low Fault AC Line Voltage High FaultCT Offset Fault AC Line Over Frequency FaultGround Current Fault DC Bus Over Voltage FaultStop Switch Fault Current Imbalance FaultSection Preventative Maintenance Periodic Maintenance TURN-ON Procedure Section Preventative MaintenanceWarranty and Certifications Section Drawings and Parts List Drawings ListOptional Accessories Page Page Page Page Page Enclosure, Upper Page Xantrex PV Series Limited Warranty and Registration