SECTION 6
PREVENTATIVE MAINTENANCE
PERIODIC MAINTENANCE
Xantrex Technology recommends that the following preventative maintenance be carried out on the
Monthly intervals or as required:
Aluminum Extrusion Heatsink
Accumulation of dirt and debris on the aluminum extrusion heatsink and fan shroud will de- crease the ability to transfer heat, which can cause the
Fan Operation
Verify proper operation of the heatsink cooling fan, located within the lower enclosure. The fan operates when the K1 contactor is closed. Remove any debris from the fan and finger guard.
Six month intervals:
(See Isolation Procedure and perform prior to the following)
Enclosure Seals
Inspect the enclosure access panel seal. If damaged, replace with equivalent closed cell foam gasket. Call your Xantrex Technology distributor for factory replacements or specifications.
Electrical Connections
Inspect the condition of all wiring within the
Mechanical electrical connections will loosen over time. This is caused primarily by thermal cycling during normal operation. As connections loosen, electrical impedance will increase at the connection, eventually leading to fire and component damage. It is critical to check all electrical connections every six months.
Enclosure
Access the enclosure and remove any accumulated dirt and debris. Vacuum enclosure whenever dust or dirt is present.
ISOLATION PROCEDURE
The following procedure should be followed to