Xantrex Technology PV-30208 important safety instructions Example of Normal System Operation

Page 21

SECTION 4 OPERATION

System Fault

System Sleep Test

System Stop

System Shutdown

EXAMPLE OF NORMAL SYSTEM OPERATION

Upon initial application of AC voltage, the LCD located on upper enclosure will display ‘Shutdown’ for approximately 15 seconds. Once the system has finished initializing, the PV-30208 will remain in standby until adequate PV voltage is available. 5 minutes after the PV start voltage has been reached, the PV-30208 will synchronize to the utility grid and begin peak power tracking the PV array. The time delay protects the inverter from excessive on/off cycling.

The PV-30208 will continue to process power until the AC output power approaches the operating losses of the inverter for a period of 5 minutes. The time delay protects the inverter from excessive on/ off cycling.

DOCUMENT: 151315

PV-30208 Photovoltaic Inverter

4-6

 

Operation and Maintenance Manual

 

Copyright 2003, Xantrex Technology

Image 21
Contents Copyright 2003, Xantrex Technology Inc South Vasco RoadTable of Contents Section Product Description Introduction Major ComponentsMain Enclosure Interconnection Standards Compliance Section Product DescriptionMatrix Bus Board Solar Control Unit SCUEquipment Symbol Section Product Description SpecificationsSection Safety Safety Features Enclosure Front Access PanelPV Ground Fault Detection Anti Island Protection Section Safety Isolation ProcedureUtility Side Isolation Transformer Requirements Torque and Wire Gauge SpecificationsInstallation Instructions Section Installation and Initial TURN-ONInstallation Floor MountedSection Installation and Initial TURN-ON Ground Fault Detection Phase-SequencingArray Grounding Section Installation and Initial TURN-ON Wiring Diagram Optional Box Frame Optional PV Conductor PV Array Ground JumperPV-30208 Inverter Initial Power Visual Inspection, PV Array WiringVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-30208System Verification Fine TuningSection Operation Description of System Operation OverviewOperating States Section Operation Operation Features Diagram Of Monopolar Configuration Section OperationBlock Current Imbalance Detection Peak Power TrackingDC Overvoltage Detection Automatic Wake Up PV Voltage OptimizationSection Operation Operator Interface Example of Normal System Operation System Fault System Sleep Test System Stop System ShutdownSection Operation System Operating Parameters User Factory Password Parameter Description Section Operation Fault Conditions Section Troubleshooting GeneralIPM Device Fault 0x0001 Through Fault DescriptionsAC Line Voltage Low Fault Section TroubleshootingAC Line Voltage High Fault AC Line Under Frequency FaultGround Current Fault AC Line Over Frequency FaultDC Bus Over Voltage Fault CT Offset FaultStop Switch Fault Current Imbalance FaultSection Preventative Maintenance Periodic Maintenance TURN-ON Procedure Section Preventative MaintenanceSection Drawings and Parts List Drawings List Warranty and CertificationsOptional Accessories Page Page Page Page Page Enclosure, Upper Page Xantrex PV Series Limited Warranty and Registration