SECTION 5
TROUBLESHOOTING
when the contactor closes. Carefully check voltage at the
(2) AC Line Voltage Low Fault (0x0100)
The utility AC voltage fell below the minimum programmed limit. There are two levels of response to low line voltage conditions. The first level of response is set to 183.0 VAC with a time delay of 2 seconds. By default, the second level is set to 104 VAC with a time delay of less than 0.1 seconds. Voltage setpoints may be modified via the operator interface program. Utility protection setpoints may only be adjusted by trained personnel with approval by both the local utility and the equipment owner.
Possible causes:
•The utility voltage fell below the allowable limit (183.0 VAC by default). Verify the utility voltage is stable and within allowable operating limits.
•There is a problem with one or more of the AC sense wires (see system schematic in Section 7).
This fault is
(3) AC Line Voltage High Fault (0x0200)
The utility AC voltage exceeded the
Possible causes:
•The utility voltage exceeded the allowable limit (228.8 VAC by default). Verify the utility voltage is stable and within allowable operating limits.
•There is a problem with one or more of the AC sense wires (see system schematic in Section 7).
The fault is
(4) AC Line Under Frequency Fault (0x0400)
The AC utility frequency fell below the minimum programmed limit. This limit is set to 59.5 Hz and the system response time limit is set to less than 0.1 seconds to insure the
Possible causes:
•The utility frequency fell below the allowable limit (59.5 Hz by default). Verify the utility frequency is stable and within allowable operating limits.
•There is a problem with one or more of the AC sense wires (see system schematic in Section 7).
DOCUMENT: 151315PV-30208 Photovoltaic Inverter5-3
Operation and Maintenance Manual
Copyright 2003, Xantrex Technology Inc.