Xantrex Technology PV-30208 important safety instructions Torque and Wire Gauge Specifications

Page 8

SECTION 3

INSTALLATION AND INITIAL TURN-ON

ISOLATION TRANSFORMER REQUIREMENTS

The PV-30208 UL1741 certification requires the use of a Xantrex Technology specified 30 kVA WYE/ WYE isolation transformer between the inverter AC output and the utility interconnection (see Appen- dix in Section 7 for transformer dimensions and specifications). This custom 30 kVA isolation trans- former is not part of the 30 kVA inverter, but can be ordered as a separate item. If maintaining the listing to UL1741 is not a requirement for your application, contact Xantrex Technology for a fact sheet de- scribing the installation options and precautions for installing this inverter in a photovoltaic system that does not require UL1741 compliance.

WARNING

Xantrex Technology requires installing an isolation transformer between the PV- 30208 inverter and the point of utility interconnection. Failure to do so could result in catastrophic damage to the PV-30208 as well as the utility distribution system and will void the product warranty.

Inverter Side Isolation Transformer Requirements

The inverter side of the isolation transformer is configured as a WYE, and is rated for 208 VAC. The neutral connection on the inverter side must be left floating. If the neutral is tied to ground, the inverter will be damaged internally at power-up.

Utility Side Isolation Transformer Requirements

The utility-side windings of the isolation transformer are configured WYE and must match the voltage at the utility inter-tie. Verify that the transformer supplied matches the voltage requirement. Also, the transformer is supplied with a neutral connection on the utility side. Connection of this utility-side neutral does not affect the operation of the inverter. Check the local utility of jurisdiction for their requirements regarding the connection of this neutral.

Contact your Xantrex Technology distributor if you have any questions regarding isolation transformer requirements.

TORQUE AND WIRE GAUGE SPECIFICATIONS

The following torque specifications are to be used on all electrical interfaces made during installation of the PV-30208.

Torque Table

Terminal Block or Bolt Size

Torque Setting

 

 

5-16 Copper Lug

52 in lbs./5.9 Nm

 

 

AC and DC Terminals

275 in lbs/31.1 Nm

 

 

DOCUMENT: 151315PV-30208 Photovoltaic Inverter3-1

Operation and Maintenance Manual

Copyright 2003, Xantrex Technology Inc.

Image 8
Contents South Vasco Road Copyright 2003, Xantrex Technology IncTable of Contents Main Enclosure Section Product Description IntroductionMajor Components Section Product Description Interconnection Standards ComplianceMatrix Bus Board Solar Control Unit SCUSection Product Description Specifications Equipment SymbolPV Ground Fault Detection Section Safety Safety FeaturesEnclosure Front Access Panel Section Safety Isolation Procedure Anti Island ProtectionTorque and Wire Gauge Specifications Utility Side Isolation Transformer RequirementsSection Installation and Initial TURN-ON Installation InstructionsInstallation Floor MountedSection Installation and Initial TURN-ON Array Grounding Ground Fault DetectionPhase-Sequencing Section Installation and Initial TURN-ON PV-30208 Inverter Wiring Diagram Optional BoxFrame Optional PV Conductor PV Array Ground Jumper Visual Inspection, PV Array Wiring Initial PowerVisual Inspection, Isolation Transformer WYE/WYE Visual Inspection, PV-30208Fine Tuning System VerificationOperating States Section Operation Description of System OperationOverview Section Operation Operation Features Block Diagram Of Monopolar ConfigurationSection Operation Peak Power Tracking Current Imbalance DetectionDC Overvoltage Detection Automatic Wake Up PV Voltage OptimizationSection Operation Operator Interface System Fault System Sleep Test System Stop System Shutdown Example of Normal System OperationSection Operation System Operating Parameters User Factory Password Parameter Description Section Operation Section Troubleshooting General Fault ConditionsFault Descriptions IPM Device Fault 0x0001 ThroughSection Troubleshooting AC Line Voltage Low FaultAC Line Voltage High Fault AC Line Under Frequency FaultAC Line Over Frequency Fault Ground Current FaultDC Bus Over Voltage Fault CT Offset FaultCurrent Imbalance Fault Stop Switch FaultSection Preventative Maintenance Periodic Maintenance Section Preventative Maintenance TURN-ON ProcedureOptional Accessories Section Drawings and Parts List Drawings ListWarranty and Certifications Page Page Page Page Page Enclosure, Upper Page Xantrex PV Series Limited Warranty and Registration