3.5 System Operating (Temperature) Range
The C4 controller operates within the limits of the system devices. There are 3 pairs
1.The range of the C4 as it is set at the factory
2The range of the controlled device (chamber or platform) as described by setup parameters F25 & F26.
3The range of the UUT (unit under test) as described by setup parameters F27 & F28.
Each of these ranges is characterized by a low limit and a high limit. The highest of the 3 low limits is the low temperature System Operation Limit. The lowest of the 3 high limits is the high temperature System Operation Limit. In other words, the controller will respect the most restrictive limits that are described by the combination of the 3 ranges listed above.
The low and high temperature System Operating Limits define the System Operating Range. The controller will not accept setpoints outside the System Operating Range and will report error conditions and stop controlling if the controlling probe(s) report a temperature too far outside that range.
Note: Probe 1 is always in the chamber airstream or platform and is always monitored for conformance with the System Operating Range. Probe 2 is monitored for conformance only if it is being used for control.
3.6 Probe Out of Range Shutdown
When the C4 is actively controlling the temperature of a chamber or platform, it frequently checks to be certain that the control temperature, as reported by any active control probe, is within the System Operating Range.
In the event that the temperature reported by the active control probe is more than 20/C, and less than 50/C, outside the controller’s System Operating Range, then the controller will presume that a “run away” condition exists. The controller will turn off all heating and cooling and stop controlling. Blowers will be left in the condition determined by setup parameter F15 (Blower
p1 lo | p1 hi |
30 | C4 Manual Rev 7.5.2 |