Sigma C4 manual Entering or Changing a Program Step, Insert Program Step, Press CLEAR/ENTRY

Page 49

6.4 Entering or Changing a Program Step

There is no difference between entering a program step and modifying an existing one.

To change any part of the program, first display the current step by pressing <DISP/CNTL>. If you wish to make changes to a step other than the current step, enter the 1 or 2 digits for the step number (0-99) and press <DISP/CNTL> again. Substep 0 of the desired step will now be displayed.

For each substep displayed, you may change the current value or accept the current value. To accept the current value and display the next substep, press <DISP/CNTL>.

To change the current value, press <CLEAR/ENTRY> to clear the old value then enter the desired new value. Pressing the <ENTER> key stores the new substep value and advances the display to the next substep. Only valid changes are allowed. Subsequent and steps and substeps may be altered in the same manner by pressing <DISP/CNTL> until the desired step is displayed.

Note: The program may only be changed when the program is not executing (run LED is off) and the controller is in the program mode (Mode swith set to PROGRAM).

Appendix 9.3 contains a template form for writing programs.

6.5 Insert Program Step

To insert a step before an existing step:

1.Enter the step number to be moved up and press <DISP/CNTL>

2.Press <CLEAR/ENTRY>

3.Press <ADV>

The display shows “ins nn”, where nn is the new incremented step number for the current step.

4.Press <ENTER> to move the current and all higher steps up 1 step and insert a new step at the current step number.

The current step will then be the new step with default values. New step.substep 0 will be displayed so you can enter your data for that step.

Note that inserting a step pushes old step 99 out of memory.

C4 Manual Rev 7.5.2

49

Image 49
Contents Sigma Systems Programmable Temperature Controller / InterfaceC4 Manual Rev Table of Contents Intelligent 2 Probe Control C4 Manual Rev C4 Manual Rev C4 Manual Rev C4 Manual Rev Models C4 & CC-3.5Explained IntroductionGeneral Description Release 7.5.2 Firmware Custom Features / Interchangeability WarningC4 vs. CC-3 Differences What’s New Firmware Uploads Forced Start from Prom Firmware Internal Error Shutdown Conditions Intelligent 2 Probe Control Probe Averaging Program Mode Step Insert & Delete RSA Remote Mode Setup Parameter Commands Front Panel Physical DescriptionMode Switch Clear Prog J1 TOP Rear Panel ConnectionsC3-5 Rel General Operation & Error Conditions200 100c 392 148f Startup DisplaysUpdating Firmware Upgrading Firmware by Prom Replacement Making the physical connection for upload Rs load Restoring Setup Parameters to Default ValuesSu res Ee busy and then su doneC4 Manual Rev Fahrenheit Operation P1fP1 lo P1 hi System Operating Temperature RangeProbe Out of Range Shutdown P1 err P1 -err Res err Internal Error Shutdown ConditionsAll res Software Probe Correction Calibration Su errStatus and Error Reporting Fail-safe System C4 Manual Rev Intelligent 2 Probe Control How Intelligent 2 Probe Control functions Preparing for Intelligent 2 Probe Control Using Intelligent 2 Probe Control Displaying Temperature Local Mode Basic OperationS1 nsp S1f nsp S1 102.6 s1fDisplaying and Changing the Setpoint Sp err Sor -sorControlling to a Setpoint C4 Manual Rev 06.0 Program ModeDescription of a Program Step 00.1 Substep Step Data 00.0Ramp time 00.2Maximizing Ramp Speed & Other Ramp Considerations Displaying Program Steps not during execution Clearing Program Memory Reinitializing program stepsInsert Program Step Entering or Changing a Program StepPress CLEAR/ENTRY Press CLEAR/ENTRY Press CLEAR/ENTRY again Delete Program stepRunning Executing a Program Program Run Time Information/Considerations Loop 007 nop2005 sor Sor Special Commands External Compressor On Common Programming Issues C4 Manual Rev EIA-232 Interface Remote ModeIEEE-488 Interface System Information Queries Command Summary by functional groupSystem Information Queries For Celsius mode For parameters numbered 0 through C4 Manual Rev Operation Information Queries & Commands REerror byteCRLF C4 Manual Rev Qccrlf PTnCRLF Setup Parameter Commands SC1 0 2.3 100 WP 6 5 5CRLF Upcrlf System Operation Commands Celsius mode Will hold the current setpoint for 1 hour and 20 minutes U1c 65.0 u1f IEEE-488 Gpib Error and Status Reporting OverviewTemperature in 20 minutes C4 Manual Rev Error/Status String Bit Definitions C4 Manual Rev Setup Mode PID controller, Integral term Adjustment not Displaying the Field Values Two Probe Mode Setup field Changing the Value of a Setup FieldAuto-start Mode Setup field Temperature Control Terms PID Setup fields 0, 10, 11 Blower Shut-off Mode Setup fieldEntering probe correction setup data C4 Manual Rev C4 Manual Rev Programming Examples & Notes Appendix00.2 00.000.3 00.4Using shortcuts to shorten program entry time DISP/CNTLSTART/STOP 9900CLEAR/ENTRY 6 Enter 04.2 04.004.3 04.407.2 07.007.3 07.4C4 Manual Rev Sigma Systems C4 Programming Worksheet Sample Command Structure for IEEE-488 Gpib Operation Disp A$ Installation and Use of TTL Outputs and Input 101 Field Calibration of Model C4 Controller102 103 TroubleshootingNoise Immunity 105 Firmware Upload Problems 107 Temperature Control PID Tuning & Problems108 109 110 111 Technical Support, Repairs & Returns U1f 102.7113 Index114 115 GpibIEEE488 Gpib 117 118 119 SRQ120