| TROUBLESHOOTING (lamps) | |
|
|
|
| |
|
|
|
| |
|
| Table 13. Lamp Troubleshooting | ||
|
|
|
|
|
| Symptom | Possible Cause |
| Solution |
|
|
|
|
|
|
| Lamp Burned Out? |
| Test the lamp in a fixture which is operating properly. |
|
|
| Replace if necessary. | |
|
|
|
| |
|
|
|
| Inspect lamp base to see if there is arcing at center |
|
| Lamp Loose in Socket? |
| contact button. Tighten lamp snugly. Check socket for |
|
|
|
| damage. Replace if defective. |
|
|
|
|
|
|
| Lamp Plugs Not Tight? |
| Check plug and receptacle. Tighten if loose. |
|
|
|
|
|
|
|
|
| Interchange ballast plugs in generator enclosure. |
|
| Defective Ballast? |
| If lamp starts, replace ballast. Check ballast wiring |
|
|
| against diagram. Check for swollen capacitor, charred | |
|
|
|
| |
|
|
|
| wiring, core and coil or other signs of excessive heat. |
|
|
|
| Check line voltage at ballast input. Voltage should |
|
| Low Voltage? |
| be within 10% of nameplate rating when operating |
|
|
| at normal load. Increase supply voltage or remove | |
|
|
|
| |
|
|
|
| external load. |
| Lamp will not start. |
|
|
|
|
|
| Proper HID lightswill perform erratically or fail to start | |
|
|
|
| on an improper ballast. The ballast nameplate data |
|
| Improper Ballast? |
| must agree with the line voltage and lamp used. |
|
|
| Improper ballast causes lamp failure. Note: Mercury | |
|
|
|
| |
|
|
|
| lightsof the same wattage will operate properly on |
|
|
|
| Metal Halide ballasts. |
|
|
|
| Operating position should agree with the lamp tech. |
|
|
|
| A |
|
| Improper Lamp Operating |
| and including the horizontal and a BD can be operated |
|
| Position (Metal Halide only)? |
| base down vertical to, approaching, but not including |
|
|
|
| the horizontal. A lamp operated beyond the specified |
|
|
|
| position may not start. |
|
|
|
|
|
|
|
|
| HID lights(High Pressure Sodium, Metal Halide, |
|
| Lamp has been Operating: Cool |
| Mercury Vapor) require from 4 to 8 minutes |
|
| Down Time Insufficient? |
| time before restarting. Switch off breaker and allow |
|
|
|
| lamp to cool. |
|
|
|
|
|
|
|
|
| Improper ballasting can cause flickering or erratic |
|
| Improper Ballast? |
| operation. In the |
| Lamp flickers and goes |
|
| start to warm up and then extinguish (cycle). |
| out intermittent or |
|
| Under certain conditions new lightsmay "cycle". |
| cycling. | New Lamp? |
| Usually after 3 tries to start at 30 to 60 second |
|
|
|
| intervals, lightswill stabilize and operate satisfactorily. |
|
|
|
|
|
|
| Defective Lamp? |
| Replace lamp. |
|
|
|
|
|