Generac Power Systems 005040-2 owner manual Control Board DIP Switch Settings

Page 18

Section 4 — Maintenance

Guardian Liquid-cooled 25 kW Generator

At this time all five red LEDs will flash for approxi- mately 10 seconds, then the engine will start and run for it’s 12 minute exercise period, then shut down. The generator will now start and run each week at the same time.

If DC power to the control board is lost, the weekly exercise setting will be lost. This is indicated by all five red LEDs continually flashing. In this state the generator will still start and run in manual mode, or automatically start and run if utility is lost while in Auto mode, but it will not perform a weekly exercise cycle.

If a failure occurs while running in this mode, the five red LEDs will stop flashing, the individual fault LED will turn on and the engine will shut down. Once the AUTO/OFF/MANUAL switch has been switch to OFF, the individual fault LED will turn OFF and the five red LEDs will begin flashing to show exercise has still not been set.

3.8CONTROL BOARD DIP SWITCH

SETTINGS

Located on the control board is an eight position DIP switch (see Figure 3.2). The eight different switches, are used to configure the control board for the spe- cific engine and governor being used and are pre-set at the factory.

If the DIP switch settings are not set correctly,

!the generator may not start or operate correct- ly.

240 VAC can be present within the control panel.

If it is necessary to select an alternate switch position, move the AUTO/OFF/MANUAL switch to the OFF position. Remove the 5 amp and 15 amp fuses in the generator control panel. Move the DIP switch position that needs to be changed to its new position. Wait five seconds, then re-install the 5 and 15 amp fuses.

The ON position is marked on the switch and the fac- tory settings are also shown in Figure 3.3.

Switch Position 1 — Selects the generator alternator output frequency and is factory pre-set for 60 Hz.

Switch Position 2 — Selects the type of transfer switch and is factory pre-set for an automatic trans- fer switch (ATS).

Switch Position 3 — Selects the type of governor control used and is factory pre-set for stepper motor control.

16 Generac® Power Systems, Inc.

Switch Position 4 — Selects the type of fuel being used and is factory pre-set for natural gas (NG).

Switch Position 5 — Selects the engine displacement and is factory pre-set for a 2.5 liter (2.5L) engine.

Switch Position 6 — Selects the number of engine cylinders and is factory pre-set for four cylinders.

Switch Position 7 — Selects the direction of rotation of the governor stepper motor and is factory pre-set for CCW rotation (rotation is observed looking at the stepper shaft as it move from closed throttle to open throttle).

Switch Position 8 — Selects whether the control is in the Normal Mode of operation or Test Mode. In the Normal Mode of operation, pre-determined governor gains are used and the gain trimpots on the control board (Gain, Stability, and Differential) are not active and have no effect on the gains. In Test Mode the gain trimpots are active and can be adjusted. See Section 3.4.

4.1MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES

A. EVERY THREE MONTHS

1.Check battery condition.

2.Inspect and test fuel system.

3.Check transfer switch.

4.Inspect exhaust system.

5.Check engine ignition system.

6.Check fan belts.

B. ONCE EVERY SIX MONTHS

1.Test Engine Safety Devices (low oil pressure, low coolant level, high coolant temperature).

C. ONCE ANNUALLY

1.Test engine governor; adjust or repair, if needed.

2.Clean, inspect generator.

3.Flush cooling system.

D. FIRST 100 OPERATING HOURS

1.Change engine oil and oil filter. After initial change, service engine oil and filter at 150 oper- ating hours or six months, whichever comes first.

2.Retorque cylinder head (see torque specs).

3.Retorque intake and exhaust manifold (see torque specs).

E. EVERY 500 OPERATING HOURS

1.Service air cleaner.

2.Check starter.

3.Check engine DC alternator.

Image 18
Contents This manual should remain with the unit ‹ HOW to Obtain Service Authorized Service Dealer Location‹ Operation and Maintenance IntroductionTable of Contents General Hazards Fire Hazards ‹ Standards IndexAutomatic System Operation Transfer SwitchGenerator Generator AC Connection Systems‹ 1.7.3 LOW Coolant Level Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch Generator Fuel SystemSpecifications UnpackingLifting the Generator Fuel Consumption Engine OIL Recommendations‹ 1.10.2 Generator Before Installation Coolant Recommendations‹ 2.1.1 Nfpa Standards Generator Mounting Support Basic Standby Electric SystemGenerator Location Emergency Circuit Isolation MethodGenerator AC Neutral Connections Using AN Engineered GTS Transfer SwitchTotal Circuit Isolation Method Grounding the GeneratorBattery Installation Preparation Before START-UP‹ 2.10.1 Vented Batteries Engineered GTS Transfer Switch ‹ 3.2.5 SET Exercise Time Switch ‹ 3.2.2 Fault Indicator Leds‹ 3.2.1 AUTO/OFF/MANUAL Switch Control Console ComponentsManual Transfer START-UP Engine Governor Adjustments ‹ 3.2.6 System Ready LEDAutomatic Operation Weekly Exercise CycleRetransfer and Shutdown Control Board DIP Switch Settings Cylinder Head Procedure Exhaust Manifold ProcedureIntake Manifold Procedure Cooling SystemOverload Protection for Engine DC Electrical System Checking Fluid Levels‹ 4.8.9 Inspect Engine Governor ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.8 Check FAN Belt ‹ 4.8.10 Changing Engine OIL‹ 4.9.3 Battery Maintenance Miscellaneous Maintenance‹ 4.9.1 Cleaning the Generator ‹ 4.9.4 Battery ReplacementScheduled Maintenance Service Maintenance Interval InformationLevel Maintenance Level Troubleshooting Points Problem Cause CorrectionGuardian Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Mount Battery Post Cover RED Hold Down Battery 2.5L FordBattery Post Cover Black Boot Battery CablePanel for Access Cover Access GEN Assy Wire 14AWG 7.5 #0 GRN/YELAssembly Cover Access Roof ACO & STD Encl 2.5L54 36 Assy Wire Fuse Holder Assy 2A 12V UL BatterySwitch ROC Dpst 125V SPD Screw Hhtt M5-0.8 X 12 BPGenerac Power Systems, Inc Ctrl PNL TOP 2.5L Ford STL Only Motor Units STARTER, 12 Volt Tank Coolant RecoveryEngine 2.5L Ford NUT HEX M10-1.5 G8 YEL CHRTo Engine GASKET, AIR Cleaner Adapter Body Carburetor AssemblyCover AIR Cleaner Bracket Fuel RegulatorLocktight Rotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumMuffler 2.5L Ford Pipe Muffler OUTPipe Exhaust 2.5L Ford Saddle 2 InchASM Motor Stepper Housing Governor ConnectorCover Connector Housing Harn GOV 2.5L FordHOSE, 2.5L Ford Lower Support Radiator 2.5L AL TALRADIATOR, 2.5L Ford VENTURI, 16 FAN 2.5L Ford RadiatorInstallation Diagram Your Warranty Rights and Obligations MANUFACTURER’S Emission Control System Warranty CoveragePURCHASER’S/OWNER’S Warranty Responsibilities Emission Control System Warranty Emission Related Parts Include the FollowingWarranty Schedule