Section 3 - Operation

Guardian Liquid-cooled 25 kW Generator

3.Under no load condition, increase the GAIN pot as much as possible without causing instability.

4.Apply 1/4, 1/2, 3/4 and full load to the unit. Decrease the GAIN pot if there is instability at any load point.

5.Under full load condition, increase the stability pot until the unit returns to 60 Hertz (or 50 Hertz in 50 Hertz applications).

6.Reduce load to 3/4, 1/2, 1/4 and no load. Decrease the stability pot if there is instability at any load point.

7.Adjust differential pot to make the recovery to load changes even faster and minimize load change undershoot and overshoot. If it is set too high, it may introduce oscillations at some load. It can be set to zero (full CCW) if a small amount causes oscillations at some load.

Figure 3.2 — Engine Governor Adjustment

Let the generator engine run at no-load for a few minutes, to stabilize internal unit temperatures.

On the generator console, set the Auto/Off/ Manual switch to Off. Wait for engine to come to a complete stop.

For transfer to utility position, refer to the Owner’s Manual of the particular transfer switch.

Turn on the utility power supply to the transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.

3.6AUTOMATIC OPERATION

To set the system for fully automatic operation, pro- ceed as follows:

Check that load circuits are connected to the utility power supply.

Set the AUTO/OFF/MANUAL switch to its AUTO position.

Set the generator main circuit breaker to its ON or CLOSED position.

3.7WEEKLY EXERCISE CYCLE

The engine control board will start and run the gen- erator once every seven days for approximately 12 minutes. If utility should fail during this exercise period, the engine control board will transfer the load to the generator output and continue to run until util- ity returns.

On the day, and at the time of day chosen for the gen- erator to exercise, set the weekly exercise cycle as fol- lows:

1.Place the AUTO/OFF/MANUAL switch in the auto position (Figure 3.3).

2.Press and hold the “Set Exercise” switch for five seconds, then release.

Figure 3.3 - “Set Exercise Time” Switch

3.5RETRANSFER AND SHUTDOWN

When utility power source voltage has been restored, electrical loads may be transferred back to that source and the generator can be shut down as fol- lows:

• Verify that utility power supply voltage to the trans-

fer switch has been positively turned Off, using

whatever means provided (such as utility main line

AUTO

OFF

MANUAL

SYSTEM READY

LOW BATTERY

LOW OIL PRESSURE LOW COOLANT LEVEL

HI COOLANT TEMPERATURE OVER SPEED

OVER CRANK

LED INDICATORS:

0F0653

OFF

ON

SET

EXERCISE

TIME

TO SET EXERCISER TIME

1)PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.

2)HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR

THREE SECONDS AND RELEASE. THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR

10 SECONDS. THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN.

RISK OF ELECTRICAL PARTS INSIDE. R

FOR STAND-BY SERV TRANSFER SWITCH IN

ATTENTION: POUR L' ICE A UN COM CAN

NAUTOMATICA INJURY REMO

circuit breaker).

• Set the generator’s main circuit breaker to its Off

or Open position.

FLASHING GREEN LED = NO UTILITY SENSE

5 FLASHING RED LED'S = EXERCISER NOT SET

(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON RED LED'S = INDIVIDUAL FAULT

(SEE OWNER'S MANUAL FOR COMPLETE DETAILS)

THIS EMERGE

Generac® Power Systems, Inc. 15

Image 17
Contents This manual should remain with the unit ‹ Operation and Maintenance Authorized Service Dealer Location‹ HOW to Obtain Service IntroductionTable of Contents General Hazards ‹ Standards Index Fire HazardsGenerator Transfer SwitchAutomatic System Operation Generator AC Connection Systems‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.3 LOW Coolant Level Switch Generator Fuel SystemLifting the Generator SpecificationsUnpacking ‹ 1.10.2 Generator Fuel ConsumptionEngine OIL Recommendations ‹ 2.1.1 Nfpa Standards Before InstallationCoolant Recommendations Generator Location Basic Standby Electric SystemGenerator Mounting Support Emergency Circuit Isolation MethodTotal Circuit Isolation Method Using AN Engineered GTS Transfer SwitchGenerator AC Neutral Connections Grounding the Generator‹ 2.10.1 Vented Batteries Battery InstallationPreparation Before START-UP Engineered GTS Transfer Switch ‹ 3.2.1 AUTO/OFF/MANUAL Switch ‹ 3.2.2 Fault Indicator Leds‹ 3.2.5 SET Exercise Time Switch Control Console Components‹ 3.2.6 System Ready LED Manual Transfer START-UP Engine Governor AdjustmentsRetransfer and Shutdown Automatic OperationWeekly Exercise Cycle Control Board DIP Switch Settings Intake Manifold Procedure Exhaust Manifold ProcedureCylinder Head Procedure Cooling SystemChecking Fluid Levels Overload Protection for Engine DC Electrical System‹ 4.8.8 Check FAN Belt ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.9 Inspect Engine Governor ‹ 4.8.10 Changing Engine OIL‹ 4.9.1 Cleaning the Generator Miscellaneous Maintenance‹ 4.9.3 Battery Maintenance ‹ 4.9.4 Battery ReplacementService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsGuardian Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Mount Battery Post Cover Black Hold Down Battery 2.5L FordBattery Post Cover RED Boot Battery CablePanel for Access Assembly Cover Access Assy Wire 14AWG 7.5 #0 GRN/YELCover Access GEN Roof ACO & STD Encl 2.5L54 36 Switch ROC Dpst 125V SPD Assy 2A 12V UL BatteryAssy Wire Fuse Holder Screw Hhtt M5-0.8 X 12 BPGenerac Power Systems, Inc Ctrl PNL TOP 2.5L Ford STL Only Motor Units Engine 2.5L Ford Tank Coolant RecoverySTARTER, 12 Volt NUT HEX M10-1.5 G8 YEL CHRTo Engine Cover AIR Cleaner Body Carburetor AssemblyGASKET, AIR Cleaner Adapter Bracket Fuel RegulatorLocktight Rotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 25KW 1P Direct HSB 2.5L Ford Rotor 39030AD1 HSB TecumPipe Exhaust 2.5L Ford Pipe Muffler OUTMuffler 2.5L Ford Saddle 2 InchCover Connector Housing Housing Governor ConnectorASM Motor Stepper Harn GOV 2.5L FordRADIATOR, 2.5L Ford Support Radiator 2.5L AL TALHOSE, 2.5L Ford Lower VENTURI, 16 FAN 2.5L Ford RadiatorInstallation Diagram PURCHASER’S/OWNER’S Warranty Responsibilities Your Warranty Rights and ObligationsMANUFACTURER’S Emission Control System Warranty Coverage Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule