Section 4 — Maintenance

Guardian Liquid-cooled 25 kW Generator

F. EVERY 800 OPERATING HOURS

1.Retorque cylinder head (see torque specs).

2.Retorque intake and exhaust manifold (see torque specs).

3.Check engine compression.

4.Check valve clearance.

4.2EXHAUST MANIFOLD PROCEDURE

1.If necessary, clean gasket surfaces on exhaust manifold and cylinder head.

2.Install exhaust manifold and exhaust manifold gasket.

3.Install fasteners.

NOTE:

Exhaust manifold fasteners must be tightened in two stages.

4.Tighten fasteners to 20-30 N-m (15-22 lb-ft) dur- ing the first stage.

5.Retighten fasteners to 60-80 N-m (44-59 lb-ft) during the second stage.

4.3INTAKE MANIFOLD PROCEDURE

1.Clean and inspect the mounting surfaces of the intake manifold and the cylinder head. Both sur- faces must be clean and flat (Figure 4.1).

2.Clean and lightly oil the manifold bolt/stud threads.

3.Install a new lower intake manifold gasket.

4.Position the lower intake manifold to the cylinder head.

5.Install retaining bolts/studs finger tight.

6.Tighten all bolts/studs to specifications in the tightening sequence shown:

First pass = 7=10 N-m (5-7 lb-ft).

Final pass = 26-38 N-m (19-28 lb-ft).

Figure 4.1 — Intake Manifold Installation

4.4CYLINDER HEAD PROCEDURE

1.Position head gasket on the block (Figure 4.2).

2.Position cylinder head to cylinder block.

3.Install 10 cylinder head bolts in numerical sequence. Tighten to 70 N-m (52 lb-ft) in sequence. Retighten to 70 N-m (52 lb-ft) in sequence. Then turn all head bolts an additional 90 - 100 degrees in sequence.

Figure 4.2 — Cylinder Head Installation

4.5COOLING SYSTEM

Air intake and outlet openings in the generator com- partment must be open and unobstructed for contin- ued proper operation. This includes such obstruc- tions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)

The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

Generac® Power Systems, Inc. 17

Image 19
Contents This manual should remain with the unit Introduction Authorized Service Dealer Location‹ Operation and Maintenance ‹ HOW to Obtain ServiceTable of Contents General Hazards ‹ Standards Index Fire HazardsGenerator AC Connection Systems Transfer SwitchGenerator Automatic System OperationGenerator Fuel System ‹ 1.7.1 LOW OIL Pressure Switch‹ 1.7.2 High Coolant Temperature Switch ‹ 1.7.3 LOW Coolant Level SwitchUnpacking SpecificationsLifting the Generator Engine OIL Recommendations Fuel Consumption‹ 1.10.2 Generator Coolant Recommendations Before Installation‹ 2.1.1 Nfpa Standards Emergency Circuit Isolation Method Basic Standby Electric SystemGenerator Location Generator Mounting SupportGrounding the Generator Using AN Engineered GTS Transfer SwitchTotal Circuit Isolation Method Generator AC Neutral ConnectionsPreparation Before START-UP Battery Installation‹ 2.10.1 Vented Batteries Engineered GTS Transfer Switch Control Console Components ‹ 3.2.2 Fault Indicator Leds‹ 3.2.1 AUTO/OFF/MANUAL Switch ‹ 3.2.5 SET Exercise Time Switch‹ 3.2.6 System Ready LED Manual Transfer START-UP Engine Governor AdjustmentsWeekly Exercise Cycle Automatic OperationRetransfer and Shutdown Control Board DIP Switch Settings Cooling System Exhaust Manifold ProcedureIntake Manifold Procedure Cylinder Head ProcedureChecking Fluid Levels Overload Protection for Engine DC Electrical System‹ 4.8.10 Changing Engine OIL ‹ 4.8.11 Changing the Engine AIR Cleaner‹ 4.8.8 Check FAN Belt ‹ 4.8.9 Inspect Engine Governor‹ 4.9.4 Battery Replacement Miscellaneous Maintenance‹ 4.9.1 Cleaning the Generator ‹ 4.9.3 Battery MaintenanceService Maintenance Interval Information Scheduled MaintenanceLevel Maintenance Level Problem Cause Correction Troubleshooting PointsGuardian Liquid-cooled 25 kW Generator Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Electrical Data Mount Boot Battery Cable Hold Down Battery 2.5L FordBattery Post Cover Black Battery Post Cover REDPanel for Access Roof ACO & STD Encl 2.5L Assy Wire 14AWG 7.5 #0 GRN/YELAssembly Cover Access Cover Access GEN54 36 Screw Hhtt M5-0.8 X 12 BP Assy 2A 12V UL BatterySwitch ROC Dpst 125V SPD Assy Wire Fuse HolderGenerac Power Systems, Inc Ctrl PNL TOP 2.5L Ford STL Only Motor Units NUT HEX M10-1.5 G8 YEL CHR Tank Coolant RecoveryEngine 2.5L Ford STARTER, 12 VoltTo Engine Bracket Fuel Regulator Body Carburetor AssemblyCover AIR Cleaner GASKET, AIR Cleaner AdapterLocktight Rotor 39030AD1 HSB Tecum Rotor 390 15KW 1P Direct HSB 2.5L FordRotor 390 20KW 1P Direct HSB 2.5L Ford Rotor 390 25KW 1P Direct HSB 2.5L FordSaddle 2 Inch Pipe Muffler OUTPipe Exhaust 2.5L Ford Muffler 2.5L FordHarn GOV 2.5L Ford Housing Governor ConnectorCover Connector Housing ASM Motor StepperVENTURI, 16 FAN 2.5L Ford Radiator Support Radiator 2.5L AL TALRADIATOR, 2.5L Ford HOSE, 2.5L Ford LowerInstallation Diagram MANUFACTURER’S Emission Control System Warranty Coverage Your Warranty Rights and ObligationsPURCHASER’S/OWNER’S Warranty Responsibilities Emission Related Parts Include the Following Emission Control System WarrantyWarranty Schedule