RACKMOUNT INSTALLATION

Chapter 2. Installation and Operation

RACKMOUNT INSTALLATION

The MX2800 STS-1 can be mounted into a standard 19-inch or

23-inch equipment rack. Follow these steps to mount your unit into a rack:

1.Prepare the MX2800 STS-1 mounting ears by scraping the paint away from the mounting ears’ portion that makes contact with the rack and the portion where the screw mounts into the side of the MX2800 STS-1.

2.Install the mounting flanges on each side of the MX2800 STS-1 at one of the three available positions.

Be sure to install the flanges with the screws provided.

3.After the flanges have been installed, position the MX2800 STS-1 at the correct location within the rack and secure the mounting flanges to the mounting rails of the rack.

4.Make all network, DTE, and power connections to the rear of the unit. See Power Up on page 2-2 for more information on making the DC power connection.

5.Using the 8-position modular to DB-9 female connector and the 8-position modular to 8-position modular cable, connect a VT 100 terminal device to the CRAFT port on the front panel of the unit.

Two MX2800 STS-1s may be stacked with no spacing between units. ADTRAN recommends 1U (1.75") of separation above and below the two stacked units. This spacing allows the unit to dissipate heat. The design of the MX2800 STS-1 uses the chassis to distribute heat generated by the unit's internal cards. This design allows the unit to operate without a cooling fan, which increases its overall reliability.