2.3

Technical Data

 

 

 

 

 

Type rating

 

 

 

 

 

PROTECT D.1000

1000 VA (pf = 0.9 lag.)

 

 

 

900 W

 

 

PROTECT D.1500

1500 VA (pf = 0.9 lag.)

 

 

 

1350 W

 

 

PROTECT D.2000

2000 VA (pf = 0.9 lag.)

 

 

 

1800 W

 

 

PROTECT D.3000

3000 VA (pf = 0.9 lag.)

 

 

 

2700 W

 

 

UPS input

1ph~ / N / PE

 

 

 

Nominal input voltage

230

Vac

 

 

Rectifier voltage range

190

Vac – 276 Vac

 

 

(without battery operation

(PROTECT D.1000 & D.1500)

 

 

100% load, pf = 0.9 lag.)

200

Vac – 276 Vac

 

 

 

(PROTECT D.2000 & D.3000)

 

 

Rectifier voltage range

180

Vac – 276 Vac

 

 

(without battery operation

(PROTECT D.1000 & D.1500)

 

 

100% load, pf = 0.8 lag.)

190

Vac – 276 Vac

 

 

EN

 

 

(PROTECT D.2000 & D.3000)

 

Rectifier voltage range

160

Vac – 276 Vac

 

 

(without battery operation

(PROTECT D.1000 & D.1500)

 

 

100% load, pf = 0.7 lag.)

180

Vac – 276 Vac

 

 

 

 

 

(PROTECT D.2000 & D.3000)

 

 

Bypass voltage range

195.5 Vac – 253 Vac

 

 

Frequency

50 Hz / 60 Hz

 

 

 

(autom. recognition or manual)

 

 

Frequency tolerance range

± 5 Hz

 

Charging rate at full load and battery charging (max.)

PROTECT D.1000

4.8 A

PROTECT D.1500

7.2 A

PROTECT D.2000

9.6 A

PROTECT D.3000

13.7 A

Circuit feedback factor

λ > 0.99

 

11