Battery

Autonomy time (for a battery charged 100% and at 25°C)

Linked

 

Autonomy time (nominal load, pf = 0.9 lag.)

 

 

 

 

 

 

 

 

 

 

battery modules

 

D.1000

 

D.1500

D. 2000

D. 3000

 

 

 

 

 

 

 

 

 

 

 

With integrated battery

 

6 min.

 

5.5 min.

6 min.

3.5 min.

 

 

 

 

 

 

 

 

 

 

 

1 extra battery module

 

31 min.

 

25 min.

33 min.

18 min.

 

 

 

 

 

 

 

 

 

 

 

2 extra battery modules

 

51 min.

 

46 min.

59 min.

34 min.

 

 

 

 

 

 

 

 

 

 

 

3 extra battery modules

 

82 min.

 

69 min.

88 min.

53 min.

 

 

 

 

 

 

 

 

 

 

 

4 extra battery modules

 

100 min.

 

90 min.

119 min.

69 min.

 

 

 

 

 

 

 

 

 

Rated direct voltage (intermediate circuit)

 

 

 

 

PROTECT D.1000

36 V

 

 

 

 

 

PROTECT D.1500

48 V

 

 

 

 

 

PROTECT D. 2000

72 V

 

 

 

 

 

PROTECT D. 3000

72 V

 

 

 

 

 

Float voltage

2.28 Vdc/cell (pre-set to 25°C)

 

 

 

charging voltage temperature dependent

EN

Setting range

2.21 Vdc/cell – 2.31 Vdc/cell

 

 

 

in 0.01V increments

 

 

 

Batt.-charge power (max.) 1.4 Adc (PROTECT D.1000 / D.1500)

 

 

 

 

1.7 Adc (PROTECT D.2000 / D.3000)

 

Battery type

Valve regulated lead battery (VRLA)

 

 

 

Special type for high-current discharge

 

PROTECT D.1000

3 blocks at 12V 9Ah

 

 

 

PROTECT D.1000 BP

2 belts at 3 blocks at 12V 9Ah

 

PROTECT D.1500

4 blocks at 12V 9Ah

 

 

 

PROTECT D.1500 BP

2 belts at 4 blocks at 12V 9Ah

 

PROTECT D.2000

6 blocks at 12V 9Ah

 

 

 

PROTECT D.3000

6 blocks at 12V 9Ah

 

 

 

PROTECT D.2030 BP

2 belts at 6 blocks at 12V 9Ah

 

Recharging times

~ 3h to 90% for internal battery

 

~9h/~15h/~21h/~27h with 1 / 2 / 3 / 4 battery extension(s)