Description | Adjustable parameters | Presetting |
Auto bypass | [enabled], [disabled] | enabled |
| “enabled” means UPS will have |
|
| bypass output when utility power on. |
|
| “disabled” means UPS will not have |
|
| bypass output when power on but |
|
| could get bypass output when UPS is |
|
| fault or overload. |
|
|
|
|
Clear Event | The number after “Total events” shows | — |
Log | how many events are currently stored |
|
| in the log. |
|
| Press the “ENTER” button for one |
|
| second to reset the event count to |
|
| zero and clear the log. |
|
|
|
|
LCD Contrast | 0 | |
| The LCD Contrast is adjustable and |
|
| the valid range is from |
|
|
|
|
Restore | [no], [yes] | No |
Factory | Setting only available in UPS |
|
Settings |
| |
mode. |
| |
|
| |
| Restoring the factory settings: |
|
| z Returns all |
|
| EEPROM settings to default |
|
| factory settings |
|
| z Resets all pending on/off |
|
| commands |
|
| z Clears the Event Log and resets |
|
| all time stamps |
|
| z Resets the battery test status |
|
| z Initiates the Self Diagnostics test |
|
|
|
|
The “Restore Factory Settings“ process is completed after i the UPS was switched off completely. Wait until the fans
stopped to allow the UPS internal EEPROM overwriting.