Description | Adjustable parameters | Presetting |
| |
Ambient | [enabled], [disabled] | enabled |
|
|
temperature | If enabled, UPS alarm when ambient |
|
|
|
high alarm |
|
|
| |
temperature >40°C |
|
|
| |
|
|
|
| |
|
|
|
| |
EPO | [normally open], [normally closed] | normally |
|
|
operation | Normally open means UPS makes a | closed |
| |
| shutdown by a closing input state. |
|
|
|
| Normally closed means UPS makes a |
|
|
|
| shutdown by an opening input state. |
|
|
|
| Setting only available in UPS |
|
|
|
| mode. |
|
|
|
|
|
|
| |
Reset | [no], [yes] | no |
|
|
Cumulative | If “no”, no action. |
|
|
|
Consumption |
|
|
| |
If “yes”, the Cumulative Consumption |
|
|
| |
kWh |
|
|
| |
kWh value is cleared and the date and |
|
|
| |
|
|
|
| |
| time stamp for this statistic is set to the |
|
|
|
| current date and time. |
|
|
|
|
|
|
| |
Battery limit | 5h,6h,...14h,15h,16h,…999h, disabled | 14h |
|
|
time | Default “14h” means when work on |
|
|
|
| battery mode for more than 14 hours, |
|
|
|
|
|
|
| |
| UPS will make bat low alarm and then |
|
| EN |
| shutdown itself 30 minutes later even |
|
| |
| battery voltage still above the |
|
|
|
| shutdown value. |
|
|
|
| Disabled means “No time limitation” |
|
|
|
|
|
|
| |
| for battery mode |
|
|
|
|
|
|
| |
Auto reboot | [enabled], [disabled] | enabled |
|
|
| Enabled means UPS will auto restart |
|
|
|
| to normal mode while utility recover |
|
|
|
| after the UPS has been shutdown for |
|
|
|
| battery low. |
|
|
|
|
|
|
| |
The UPS automatically restarts if utility returns after the output was shut |
| |||
off due to exhausted batteries, a shutdown input signal, or automatic |
| |||
shutdown command. |
|
|
| |
You can set the load segment for the amount of time to delay the restart |
| |||
once utility returns, using the “Automatic Start Delay” setting. You can |
| |||
also configure UPS restart to depend on the battery charge level, using |
| |||
the “Battery Charge Capabilitiy % to Restart” setting. |
|
|
| |
|
|
|
|
|
53