Alarm

Possible cause

Remark/ Action

 

 

 

Charger Failure

A battery charger fault

The UPS turns off the

(Alarm #34)

has been detected.

charger until the next

 

power recycle.

Continuous Alarm

 

 

Contact your service

 

 

 

 

representative.

 

 

 

Output Short Circuit

The uninterruptible

The uninterruptible

(Alarm #58)

power supply has

power supply operates

detected abnormal

as a constant-current

Intermittent Alarm

low impedance that

source (4.4 x IN) and

 

 

placed on its output

shuts down after five

 

and considers it a

cycles (100ms).

 

short circuit.

 

 

 

 

Heat sink Over

The uninterruptible

Make sure that the

Temperature

power supply has

fans are spinning and

(Alarm #73)

detected that one of

that the air intake

its heat sinks has

vents on the

Intermittent Alarm

exceeded the

uninterruptible power

 

 

maximum defined

supply are not

 

operating

blocked. After the

 

temperature.

maximum

 

Possible fan failure

temperature is

 

reached, the

 

(see below).

 

uninterruptible power

 

 

 

 

supply shuts down.

 

 

 

Fan Failure

The uninterruptible

This is an alarm only.

(Alarm #193)

power supply has

Contact your service

detected that one or

representative

Continuous Alarm

more fans are not

immediately and

 

 

functioning correctly.

remove the load.

 

 

 

Fatal EEPROM Fault

There is EEPROM

Contact your service

(Alarm #53)

data corruption due

representative.

to a failed device or

 

Continuous Alarm

 

incorrect flash upgrade.

 

 

 

 

 

 

62