Description | Adjustable parameters | Presetting |
Relay | [UPS ok], [on bypass], | UPS ok |
configuration | [on Economical mode (ECO)], |
|
| [on High efficiency mode (ECO+)], |
|
| [on battery], [battery low], |
|
| [battery fault], [battery missing], |
|
| [Fan fault], [Summary Alarm] |
|
|
|
|
Control | [enabled] [disabled] | enabled |
Commands | If Enabled, control commands are |
|
from |
| |
accepted through Serial & USB port |
| |
Serial Port |
| |
and cards in the communication slot. |
| |
|
| |
| If Disabled, configuration and load |
|
| control commands are restricted to |
|
| LCD panel only. |
|
|
|
|
Output | [200V], [208V], [220V], [230V], [240V], | |
Voltage |
| |
| Setting only available in UPS |
|
| mode. |
|
|
|
|
Output | [50Hz], [60Hz], | |
Frequency | Setting only available in UPS |
|
| mode. |
|
|
|
|
Load Alarm | [10%], [20%], [30%], ...[100%] | 100% |
Level | If 100%, the UPS issues an Output |
|
(Overload) |
| |
Overload alarm at load > 100%. |
| |
|
| |
| NOTE: Output Overload Level 1 by |
|
| default is set to 100% and is |
|
| configurable from 10% to |
|
| 100% in 10% increments |
|
| through the LCD setting menu. |
|
| This allows customers to be |
|
| alerted before the UPS has |
|
| reached its rated capacity |
|
| limits. |
|
Power | [High performance mode (normal)], | normal |
strategy | [Economical mode (ECO)], |
|
| [High efficiency mode (ECO+)], |
|
| [converter] |
|
| Setting only available in UPS |
|
| mode. |
|
|
|
|
50