Description

Adjustable parameters

Presetting

Relay

[UPS ok], [on bypass],

UPS ok

configuration

[on Economical mode (ECO)],

 

 

[on High efficiency mode (ECO+)],

 

 

[on battery], [battery low],

 

 

[battery fault], [battery missing],

 

 

[Fan fault], [Summary Alarm]

 

 

 

 

Control

[enabled] [disabled]

enabled

Commands

If Enabled, control commands are

 

from

 

accepted through Serial & USB port

 

Serial Port

 

and cards in the communication slot.

 

 

 

 

If Disabled, configuration and load

 

 

control commands are restricted to

 

 

LCD panel only.

 

 

 

 

Output

[200V], [208V], [220V], [230V], [240V],

auto-sensing

Voltage

[auto-sensing]

 

 

Setting only available in UPS stand-by

 

 

mode.

 

 

 

 

Output

[50Hz], [60Hz], [auto-sensing]

auto-sensing

Frequency

Setting only available in UPS stand-by

 

 

mode.

 

 

 

 

Load Alarm

[10%], [20%], [30%], ...[100%]

100%

Level

If 100%, the UPS issues an Output

 

(Overload)

 

Overload alarm at load > 100%.

 

 

 

 

NOTE: Output Overload Level 1 by

 

 

default is set to 100% and is

 

 

configurable from 10% to

 

 

100% in 10% increments

 

 

through the LCD setting menu.

 

 

This allows customers to be

 

 

alerted before the UPS has

 

 

reached its rated capacity

 

 

limits.

 

Power

[High performance mode (normal)],

normal

strategy

[Economical mode (ECO)],

 

 

[High efficiency mode (ECO+)],

 

 

[converter]

 

 

Setting only available in UPS stand-by

 

 

mode.

 

 

 

 

50