Description

Adjustable parameters

Presetting

Start w/o

[enabled], [disabled]

enabled

mains

cold Start

 

 

 

 

 

 

Battery

[disabled], [10%], [20%], ...[100%]

disabled

Saving Mode

On battery operation the UPS output

 

 

is turned off as soon as the battery

 

 

capacity is below the selected level.

 

Site Wiring

[enabled], [disabled]

disabled

Fault Alarm

 

 

 

 

 

Charger output

Float charging voltage per battery cell

2.28V

voltage / cell

2.21V, 2.22V, 2.23V, 2.24V, 2.25V, 2.26V,

 

 

2.27V, 2.28V, 2.29V, 2.30V, 2.31V

 

 

 

 

Battery Charge

[0%], [10%], [20%], …[100%]

0

capability % to

When enabled, automatic restart is

 

Restart

 

made when the battery charge state

 

 

reaches the selected level.

 

 

If set 0, the feature is disabled.

 

Automatic

[enabled], [disabled]

enabled

battery

 

 

support tests

 

 

 

 

 

Periodic

[daily], [weekly], [monthly]

weekly

Battery Tests

 

 

 

 

 

Automatic battery tests run according to “periodic battery test”, unless disabled. During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under the existing load.

i

The “UPS on Battery” notice and the “Battery Low” alarm

do not activate during a battery test.

 

NOTE: For automatic battery tests to run:

The “Automatic Battery Support Tests” setting must be enabled.

The UPS must be in Normal mode, with no active alarms.

The batteries must be fully charged.

The bypass voltage must be acceptable.

To pass the battery test, the battery voltage must remain above the threshold value during discharge.