Description | Adjustable parameters | Presetting |
Start w/o | [enabled], [disabled] | enabled |
mains | cold Start |
|
|
| |
|
|
|
Battery | [disabled], [10%], [20%], ...[100%] | disabled |
Saving Mode | On battery operation the UPS output |
|
| is turned off as soon as the battery |
|
| capacity is below the selected level. |
|
Site Wiring | [enabled], [disabled] | disabled |
Fault Alarm |
|
|
|
|
|
Charger output | Float charging voltage per battery cell | 2.28V |
voltage / cell | 2.21V, 2.22V, 2.23V, 2.24V, 2.25V, 2.26V, |
|
| 2.27V, 2.28V, 2.29V, 2.30V, 2.31V |
|
|
|
|
Battery Charge | [0%], [10%], [20%], …[100%] | 0 |
capability % to | When enabled, automatic restart is |
|
Restart |
| |
made when the battery charge state |
| |
| reaches the selected level. |
|
| If set 0, the feature is disabled. |
|
Automatic | [enabled], [disabled] | enabled |
battery |
|
|
support tests |
|
|
|
|
|
Periodic | [daily], [weekly], [monthly] | weekly |
Battery Tests |
|
|
|
|
|
Automatic battery tests run according to “periodic battery test”, unless disabled. During the test, the UPS transfers to Battery mode and discharges the batteries for 10 seconds under the existing load.
i | The “UPS on Battery” notice and the “Battery Low” alarm | |
do not activate during a battery test. | ||
|
NOTE: For automatic battery tests to run:
•The “Automatic Battery Support Tests” setting must be enabled.
•The UPS must be in Normal mode, with no active alarms.
•The batteries must be fully charged.
•The bypass voltage must be acceptable.
To pass the battery test, the battery voltage must remain above the threshold value during discharge.