UPS output

Nominal output voltage

200/208/220/230/240 Vac ± 2%

 

Power reduction:

 

10% at 208V, 20% at 200V

Nominal frequency

50 Hz / 60 Hz ± 0.25 Hz

 

(Tolerance in battery mode

 

or free running in frequency

 

changer mode)

Synchronization range

50 Hz or 60 Hz ± 3 Hz

Synchronization speed

1 Hz / s

Power factor range

0.8 lag. to 0.9 cap.

 

for full power output

 

Power reduction:

 

10% to 0.5lag., 20% to 0.5 cap.

Voltage waveform

Sine, distortion

 

< 3% THD (linear load)

 

< 6% THD (non-linear load)

Crest factor

3:1

Overload behavior

to 110% continuously;

with mains supply

≥ 110% – <130% for 5 min.

 

≥ 130% – <150% for 15 s

 

≥ 150% for 300 ms

Overload behavior

to 102% continuously;

with battery operation

≥ 110% – <130% for 12 s

 

≥ 130% – <150% for 2 s

 

≥ 150% for 100 ms

Short-circuit behaviour

4.4 x IN for 100 ms

12