AEG PV.500-MH manual Connection to MultiCom interface

Models: PV.500-MH

1 68
Download 68 pages 42.91 Kb
Page 56
Image 56
Connection to MultiCom interface

Protect PV.500-MH Operating Instructions

X7:

Connection to MultiCom interface

S1:

Service switch

X3:

When a signal is received, the contact between the two

 

contact points with the lower numbers is closed (normal-

 

ly open or "NO").

X4:

When a signal is received, the contact between the two

 

contact points with the lowest numbers is open (normally

 

closed or "NC").

X5:

The control signal is active when the input is bridged

 

(normally open). The inverter is switched off.

The following default signals are used for remote signalling:

X3.1-2 3

Inverter feed operation

(NO)

X3.4-5 6

DC distribution signal*

(NO)

X3.7-8 9

AC distribution signal*

(NO)

X3.10-11 12 Incoming mains fault

(NO)

X4.1 2-3

Inverter fault*

(NC)

X5.1-2

Inverter remote switch-off

(NO)

*): Collective signals that contain all messages and faults

Figure 23 shows the normally closed contact in the state that ap- plies when the signal is not active (normally open) or the voltage is zero.

The service switch enables maintenance work on the unit to be signalled to the MultiCom interface using various protocols.

56 of 68

80000043212 BAL

Page 56
Image 56
AEG PV.500-MH manual Connection to MultiCom interface