Protect PV.500-MH Operating Instructions

If you are using a different/in-house monitoring system, you can adjust the transmission parameters and the slave address of the Modbus interface to suit your requirements via port 1 (X2). We would be happy to provide you with the Modbus unit profile on re- quest.

7.1.4.1 Configuration Preparations

You will need a 1:1 data line and a PC.

For this configuration, you must connect the PC to the MultiCom interface (X2) via the data line and start a terminal program, e.g. Hyperterminal, on the PC.

Setting the terminal program:

Data transmission:

COMx, 9600 baud/8 data bits/1 stop bit

 

No parity/no protocol

Terminal emulation:

VT100

You can then start the configuration by pressing the “S1” button on the MultiCom interface. Ensure that no communication has taken place via interfaces X2/X5 for at least 10 seconds before doing so.

Initiation of the configuration is displayed by the two LEDs flashing on the MultiCom interface and the following display on the termi- nal:

“PRESS <CR> FOR CONFIGURATION WHILE LED IS FLASHING”

The configuration starts provided you press the <ENTER> key (<CR>) within 30 seconds. The configuration main menu opens:

Figure 18

Main menu

If the configuration does not start, you must wait for 10 seconds and then repeat the procedure. Make sure that no data is received via the X2/X5 interfaces during this time.

Press the following key in the main menu:

<CR> to save the set values, exit the configuration and activate the MultiCom interface.

<ESC> to cancel the configuration.

<2> to access the X5 data transmission configuration. <4> to access the X5 data protocol configuration.

48 of 68

80000043212 BAL

Page 48
Image 48
AEG PV.500-MH manual Configuration Preparations, Setting the terminal program