Performance Notes

The following SpeedDome Ultra VII features are not supported with the Pelco protocols:

PAL video format. This will be supported after further testing.

Long line length applications that require video amplifiers or fiber optics.

Address Settings

The dome must have the correct address setting to operate with Pelco Coaxitron and “P” protocols. For Coaxitron protocol, the address must be set to 893. For “P” protocol, the address setting is based upon the baud rate setting:

For 2400 baud, the x100 switch must be set to 6; the x10 and x1 switches may be set to any number.

For 4800 baud, the x100 switch must be set to 0; the x10 and x1 switches may be set to any number.

For 9600 baud, the x100 switch must be set to 7, the x10 and x1 switches may set to any number.

Tested Pelco Equipment

The following Pelco equipment has been tested with SpeedDome Ultra VII:

Pelco 9760CTX

Pelco MPT 9500

Supported Pelco Features

SpeedDome Ultra VII supports Left and Right Scan Limits, Auto Scan, Frame Scan and Random Scan when installed under the Pelco Coaxitron and “P” Protocol environment. The following commands are supported:

If you want to...

Use...

Program the Left Scan Limit

Set Preset 92

Program the Right Scan Limit

Set Preset 93

Activate Auto Scan

Call Preset 99

 

 

Activate Frame Scan

Call Preset 98

 

 

Activate Random Scan

Call Preset 97

 

 

Deactivate Auto, Frame or Random Scan

Call Preset 96

 

 

C–4

SpeedDome Ultra VII Operator's Manual