American Power Conversion PD60H5HK1 Loading Limits, Voltage Limits, Other Limits, Global Alarm

Models: PDRPPH1000 PD60H5HK1

1 76
Download 76 pages 8.59 Kb
Page 23
Image 23

PDU Display Interface

Alarm Setup

Use this option of the Alarms screen to access the following options:

Loading Limits

Configure the following in amps and as a percentage of full load:

 

Out High: The upper limit for output current

 

Out Low: The lower limit for output current

 

Out Neut: The upper limit for current on the neutral wire for

 

 

the output phases

Voltage Limits

Configure the following as a percentage under or over the rated

 

voltage:

 

Input: The allowed range for input voltage

 

Output: The allowed range for output voltage

Other Limits

Configure this limit:

 

 

Frequency: The frequency variation, in hertz, that is acceptable

 

 

for the output current.

Global Alarm

Set all the loading limits or all the voltage limits simultaneously as a

Config

percentage of full load:

 

Load Limits: Set the same percentage upper limit for output

 

 

current and current on the neutral wire, and the lower limit for

 

 

output current. (Use the Loading Limits option to set these

 

 

thresholds individually.)

Volt Limits: Set the same percentage for the high and low thresholds for input and output voltage. (Use the Voltage Limits option to set these thresholds individually.)

Select Apply Now and then YES to implement your changes.

Alarm Beeper

Use this option of the Alarms screen to turn the alarm beeper ON or OFF.

60kW InfraStruXure PDU—Operation and Configuration

15

Page 23
Image 23
American Power Conversion PD60H5HK1, PDRPPH1000 manual Loading Limits, Voltage Limits, Other Limits, Global Alarm, Config