Customizing and Updating the PDU

4.At the front of the PDU, connect the power cord’s individual wires:

a.If you have branch current monitoring installed, route the phase conductor through a current sensor.

b.Connect the line wire to the circuit breaker.

c.Connect the neutral wire to the closest open termination point on the Neutral Bar (N).

d.Connect the PE wire to the closest open termination point on the PE Bar (PE).

N

PE

46

60kW InfraStruXure PDU—Operation and Configuration