American Power Conversion PD60H5HK1, PDRPPH1000 manual Rear view of PDU with transformer interior

Models: PDRPPH1000 PD60H5HK1

1 76
Download 76 pages 8.59 Kb
Page 33
Image 33

Overview

Rear view of PDU with transformer (interior)

The Main input switch connects to your main power source. The switch accepts 400V input and requires L1, L2, L3, and PE input

conductors.

The PDU monitoring unit has several current and voltage monitoring boards that report to a central board assembly located in the PDU monitoring unit. The PDU monitoring unit has one 10BaseT (Cat-5) connection to the Information Controller hub (or switch), four relay output connections, four input contact connections, and one EPO input connection. Make these connections at the user connection plate located on the roof of the PDU. See “PDU monitoring unit” on page 27 and “User connection plate” on page 28 for a more detailed

description.

The output of the optional isolation input transformer feeds the input circuit breaker of the maintenance bypass panel.

Note: The secondary side of the optional isolation/input transformer should be provided with a suitable separate connection to an earth electrode.

60kW InfraStruXure PDU—Operation and Configuration

25

Page 33
Image 33
American Power Conversion PD60H5HK1, PDRPPH1000 manual Rear view of PDU with transformer interior