Specifications

InfraStruXure PDU

Electrical

With Transformer

Without Transformer

 

 

 

 

 

 

Output

 

 

 

 

Voltage AC

L1, L2, L3, N, PE

400/230V: 3W, N, PE

 

Full Load Rating

60kVA

100A

 

Nominal Current

167A

180A

 

Number of Distribution Panels

2 × 225A, 42-position

 

 

 

Max. Distribution Breaker Size

150AT

150AT

 

Main Breaker

175A MCCB, 100% rated

225A MCCB

 

Input

 

 

 

 

Nominal Voltage

400V

400/230V

 

Frequency

57–63Hz

47–70Hz

 

Voltage AC

L1, L2, L3, PE

400/230V: 3W, N, PE (WYE)

 

Nominal Current

167A

100A

 

Disconnect

225A molded case switch

N/A

 

 

 

 

 

 

Physical

 

 

 

 

 

 

 

 

 

Dimensions (H×W ×D)

 

 

 

 

PDU

2159 × 610 × 864 mm

2159 × 610 × 864 mm

 

 

(85 × 24 × 34in)

(85 × 24 × 34in)

 

Weight

 

 

 

 

PDU only

410kg (904lb)

204kg (450lb)

 

PDU with 28 cables

556kg (1226lb)

351kg (774lb)

 

 

 

 

 

 

Relay Outputs

 

 

 

 

 

 

 

 

 

Nominal switching capacity

1A at 30VDC

 

 

 

Maximum switching power

30W

 

 

 

Maximum switching voltage

60VDC

 

 

 

Maximum switching current

2ADC

 

 

 

Maximum carrying current

2ADC

 

 

 

Surge Ratings

2kV per Bellcore TA-NWT-001089

 

 

1.5kV per FCC part 68

 

 

 

 

 

 

 

 