Overview

Front view (interior)

The two 42-position circuit breaker panels provide 84 total single pole positions. Each single pole provides power at 230 volts L-N. The amperage each position provides depends on the size of the circuit breaker

used.

The document pocket provides storage of documents relating to the circuit breaker panels, such as the PDU Panel Board Schedules

(provided).

The Main Output breaker protects the distribution circuit breaker panels. Note: On PDUs without a transformer, this breaker is located in the rear

interior of the PDU (same as the Main Input).

The user connection plate is connected to the PDU monitoring unit, and provides easy access to input contact, relay output, network, and EPO connections. Make connections from inside the enclosure, and route wires through the knockout provided on the plate.