Overview

PDU monitoring unit

This connection provides the input power for the PDU monitoring unit. The power is supplied by the monitoring unit circuit breaker on the front of the PDU. If the panel is on, and the monitoring unit circuit breaker is closed, the monitoring

unit is powered.

Connects to sensors monitoring values such as voltage, current, and power.

Digital input sensing for monitoring such as circuit breaker

status, transformer temperature, fans, etc.

The Display port (RJ-45) connects the PDU monitoring unit to

the PDU display interface.

The Power LED indicates whether the monitoring unit is receiving power.

Use the Console port (DB-9) to connect a laptop computer to the monitoring unit using an appropriate communication cable (APC part number 940-0103). This port is used to configure

items relating to servicing the PDU.

EPO DIP switches configure the EPO input for the type of EPO switch that is connected—Normally Open (NO) or

Normally Closed (NC).

When the EPO Arm/Test rocker is in the Test position, engaging the EPO switch will not cause the load to be powered off. When the rocker is in the Armed position, engaging the EPO switch will cause the PDU’s main input switch to be switched OFF. See “How to Test the Emergency Power Off Switch” on page 49 for more information on testing the EPO

switch.

The EPO Armed LED is green when the rocker switch is in the Armed position. The LED is dark when the rocker is in the Test

position.

The EPO Tripped LED is red when the EPO switch is engaged (the EPO button is pressed), regardless of the state of the EPO

Arm/Test rocker switch,

The Reset button resets the network processor; it does not reset the PDU or PDU monitoring unit.

885-2288

CONTACTSEPO/USER

 

UPS

2 1

15 14

 

 

 

TO

4 3

16

 

 

 

6

17

 

 

 

5

 

 

 

 

 

 

1 8

 

 

 

 

7

 

 

 

 

 

 

20

 

 

 

 

8

 

 

 

 

 

 

2 1

 

 

 

 

9

 

 

 

 

 

10

22

 

 

 

LINK RX/TX

23

 

 

 

11

 

 

 

 

12

24

 

 

 

 

25

 

 

NETWORK

10=GRN 100=ORN

13

 

 

 

STATUS

DISPLAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ARMED

RS-232 CONSOLEPORT

 

9600-8 N-1

 

 

NC

 

 

TEST

 

 

 

 

NO

 

 

 

 

Connect to the InfraStruXure Manager through the network port.

Not used on this model PDU.

The optional User/EPO Contacts port is connected to wire harnesses that connect the User Connection Plate in the roof (or floor) of the PDU. The port allows for relay outputs (4), input contacts (4), and an EPO input (1). See “Contacts Screen” on page 10 and “How to Test the Emergency Power Off Switch” on page 49 for more information.

 

The branch current monitoring boards connect to the Branch Current Monitor ports (RJ-11). These ports

 

are on the top side of the PDU monitoring unit, and are labeled on the face of the unit. Each port corresponds

 

to a section of circuit breakers on the PDU distribution circuit breaker panel: upper left=[01..41]; upper

Note

right=[02..42]; lower left=[43..83]; lower right=[44..84].

60kW InfraStruXure PDU—Operation and Configuration

27

Page 35
Image 35
American Power Conversion PD60H5HK1, PDRPPH1000 manual PDU monitoring unit, Arm/Test rocker switch