Config Screen

System/Network

Use this option of the Config screen to access these options:

System Password

Password: Change the system password required to access

 

 

protected screens and fields in the display interface. Enter a

 

 

string of up to eight alphanumeric characters, followed by the

 

 

underline character (_) to indicate the end of the string. By

 

 

default, no password is required.

 

Time-out: Set the time that the display interface waits for user

 

 

input before it reverts to the initial scrolling of status screens.

 

 

Select 1, 2, 5, 10 (the default), or 30 minutes; or 1, 2, or 4 hours,

 

 

or Forever.

 

Invalidate NOW: Re-enter the system password for viewing

 

 

password-protected screens.

Date/Time

Date: Set in the following format: dd-mmm yyyy.

 

Time: Set in the following format: hh:mm:ss.

Local Interface

Contrast: Set the screen contrast for the LCD. Select from 1

 

 

(high contrast) to 8 (low contrast).

 

Key Click: Choose On for an audible click whenever you press

 

 

a navigation key. Choose Off to disable the key click.

 

Beeper: Select High, Medium, Low, or Off to adjust the

 

 

loudness of the audible beeper and the key click.

Network Address The following values are set by the Information Controller during initial configuration:

IP: The System IP address, which the domain name server translates into a domain name.

Mask: The subnet mask, which identifies the subnetwork on which the PDU operates.

GW: The Gateway address. This is the physical address of the PDU, expressed as a 48-bit hexadecimal number.