Overview

User connection plate

For a detailed description of the user connection plate, see () on page 24. For clarity, the user connection plate in the following illustration is shown in greater detail.

!

USER

©

MADE USA

 

1

2

3

4

 

 

Contact Inputs

 

 

ATS 0 ATS1 ATS 2 ATS EN

– +

 

 

EPO 24V

EPO

Contact Outputs

AC/DC

Contact

!

Connect the InfraStruXure PDU to the network or the InfraStruXure Manager through the ethernet port.

The user connection plate has four input contact connections for monitoring Normally Open (NO) or Normally Closed (NC) dry contacts. See page 12 and page 48 for more information.

The user connection plate has four relay output connections for Normally Open (NO) or Normally Closed (NC) dry contacts. See page 12 and page 48 for more information.

Connect an Emergency Power Off (EPO) switch at one of three choices of EPO connections (24VDC, 24VAC, or contact closure).

28

60kW InfraStruXure PDU—Operation and Configuration

Page 36
Image 36
American Power Conversion PDRPPH1000, PD60H5HK1 manual User connection plate