Shutdown (cont.)

Multi-bypass modular UPS

shutdown each UPS (see section "shutdown of a unit");

the load is supplied via the Mains 2 of each UPS;

close switch Q3BP on each UPS, the load is supplied by the Mains 2, via the bypass lines (Q3BP) of each UPS;

open switches Q5N, Q4S, Q1 and QF1 on each UPS, the situation is that shown in the figure opposite;

the UPSs are de-energised once the capacitors have discharged.

Modular UPS 1

Q3BP

 

 

static switch

 

 

Q4S

 

rectifier-

inverter

 

charger

 

Q1

Q5N

 

mains 1

 

 

 

QF1

 

mains 2

battery

 

Modular UPS 2

Q3BP

load

 

 

 

 

static switch

 

 

Q4S

 

rectifier-

inverter

 

charger

 

Q1

Q5N

 

mains 1

 

 

 

QF1

 

 

battery

 

Frequency converters

(no Mains 2)

Shutdown of the inverters results in the interruption of the load;

shut down each inverter (see the "shutdown of a unit" section);

open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;

QF1

ON OFF

(I)

(0)

Q1

ON OFF

(I)

(0)

Q5N

ON

(I)

the system is powered down (except the Mains 1 cables upstream from switch Q1). A full powering down requires the opening of the upstream protection device on Mains 1.

Parallel UPSs with SSC

(with Mains 2)

shut down each inverter (see the "shutdown of a unit" section);

carry out the maintenance bypass operation in the Static Switch Cubicle (the load will be directly supplied by Mains 2 via maintenance bypass switch Q3BP);

close switch Q3BP and open switches Q5N and Q4S in the "static switch" cubicle;

open fuse switches Q1 and Q2 in the Static Switch Cubicle;

open battery circuit breaker QF1 in each UPS (except for frequency converters without a battery);

open input switch Q1 for each UPS;

the UPSs are powered down (except

the Mains cables upstream from switches Q1, Q4S and Q3BP) and the load is supplied by Mains 2.

All the lights on the control panel are off. A full powering down requires load shutdown and the opening of the upstream protection devices on Mains 1 and 2.

Buzzer reset

first determine the cause of the alarm;

press the "buzzer reset" button 11 on the hidden control panel on the concerned cubicle.

The buzzer stops, but a new alarm will set it off again.