Maintenance (cont.)
Modular UPS with external maintenance bypass
(figure 31)
To service a number of modular UPSs with an external maintenance bypass, it is necessary to isolate them.
◗isolate the UPSs
Proceed in the following order:
◗shut down each inverter (press the "inverter off" button 7 for three seconds),
◗switch to the maintenance bypass whereby the load will be directly supplied by Mains 2 via Q3BP (close Q3BP, then open Q5 in the maintenance bypass cubicle),
◗open input switch Q4S on each UPS;
◗isolate each UPS from Mains 2 by opening the upstream protection devices,
◗open input switch Q1 on each UPS,
◗open output switch Q5N on each UPS.
The UPSs are
◗start-up
Once servicing is completed, proceed in the following order:
◗close the input switches Q1 and Q4S on each UPS,
◗close output switch Q5N on each UPS,
◗close output switch Q5N in the maintenance bypass cubicle,
◗open switch Q3BP in the maintenance bypass cubicle,
◗close battery circuit breaker Q1 on each UPS,
External maintenance bypass | |
| Q3BP |
Modular UPS 1 |
|
Q4S | static switch |
| |
mains 2 |
|
rectifier- | inverter |
charger | |
Q1 | Q5N |
mains 1 |
|
QF1 |
|
| battery |
Modular UPS 2 | load |
| |
| Q5N |
Q4S | static switch |
| |
mains 2 |
|
rectifier- | inverter |
charger | |
Q1 | Q5N |
mains 1 |
|
QF1 |
|
| battery |
Fig. 31
◗ start all the inverters (press the | Note. It is strongly advised to call on | |
our | ||
"inverter on" button 6 ). | ||
these operations. | ||
The UPSs all come on line at the same | ||
time if they are sufficient in number to |
| |
supply the load. |
|
Frequency converter or parallel UPS with SSC
(figure 32)
During maintenance, the concerned UPS or converter must be isolated from Mains 1, its battery and the output circuits of the other units.
◗inverter isolation
Proceed in the following order:
◗shut down the inverter (press the "inverter off" button 7 for 3 seconds),
◗open isolating switches Q5N, QF1 and Q1 for that line.
The unit is powered down once the capacitors have discharged (a few minutes).
In redundant systems with at least one redundant UPS, the other UPSs (or converters) ensure continuity of power to the load.
Q1
mains 1
Q1
mains 1
Q1
mains 1
QF1
QF1
QF1
Q5N
Q5N
load
Q5N
Fig. 32: frequency converter exemple
Page 32 - 6739380EN/JC