Inverter On/Off commands
These commands may be accessed only via the master display. When the "I/O" button is pressed, the series of
"Monitor" alphanumeric display (cont.)
Display for the inverter On/Off commands
screens in the figure opposite is displayed.
Note:
◗these commands do not concern the Static Switch Cubicle. The "I/O" button on the "static switch" cubicle produces the message:
COMMAND INVALID
STATIC SWITCH MODUL
◗the "I/O" button on a slave display monitor produces the message:
COMMAND INVALID
ON SLAVE DISPLAY
◗if the On/Off commands have not been validated (by the
or
START INVERTER ?
*=YES >=ESCAPE
*
initial screen
STOP INVERTER ?
*=YES >=ESCAPE
*
initial screen
Direct access to the function by pressing the "I/O" button .
This screen is displayed if the inverter is already off. It is a prompt to press the "*" button to confirm
PROCESSING
…
This screen is displayed if the inverter is on. It is a prompt to press the "*" button to confirm shutdown.
If the transfer to Mains 2 conditions are not correct, the following screen is displayed a few seconds:
COMMAND REFUSED
TRANSFER IMPOSSIBLE
Following confirmation of the command, the system automatically returns to the initial screen.
COMMAND INVALID
CONFIGURATION
◗ if a "Soft Tunor" session is in |
|
|
|
COMMAND INVALID |
| ||
progress (initiated by |
|
| |
support technicians), pressing the "I/O" |
| SOFT TUNOR |
|
button produces the message: |
|
|
|
|
|
Language, display contrast and buzzer volume settings
These settings may be accessed by pressing the "settings" button.
Display of the settings selection screens
The series of screens in the figure opposite is displayed.
LANGUAGE = ENGLISH
*=CONFIRM.
*
DISPLAY CONTRAST >=SELECT *=CONFIRM.
*
BUZZER VOLUME >=SELECT *=CONFIRM.
*
Direct access to the function by pressing the "settings" button.
Selection of the display language: English, French, German, Italian, Spanish, Dutch, Swedish, Finnish, Portuguese.
This screen is a prompt to set the display contrast by successively pressing the ">" button. When the setting is confirmed by pressing the "*" button, the system goes on to the buzzer.
When this screen is displayed, the buzzer automatically turns on. Press the ">" button several times to adjust the volume. After confirmation of the buzzer volume by the "*" button, the system automatically returns to the initial screen.
initial screen