Inverter On/Off commands

These commands may be accessed only via the master display. When the "I/O" button is pressed, the series of

"Monitor" alphanumeric display (cont.)

Display for the inverter On/Off commands

screens in the figure opposite is displayed.

Note:

these commands do not concern the Static Switch Cubicle. The "I/O" button on the "static switch" cubicle produces the message:

COMMAND INVALID

STATIC SWITCH MODUL

the "I/O" button on a slave display monitor produces the message:

COMMAND INVALID

ON SLAVE DISPLAY

if the On/Off commands have not been validated (by the after-sales support technicians), pressing the "I/O" button produces the message:

or

START INVERTER ?

*=YES >=ESCAPE

*

initial screen

STOP INVERTER ?

*=YES >=ESCAPE

*

initial screen

Direct access to the function by pressing the "I/O" button .

This screen is displayed if the inverter is already off. It is a prompt to press the "*" button to confirm start-up. During start-up, the following screen is displayed:

PROCESSING

This screen is displayed if the inverter is on. It is a prompt to press the "*" button to confirm shutdown.

If the transfer to Mains 2 conditions are not correct, the following screen is displayed a few seconds:

COMMAND REFUSED

TRANSFER IMPOSSIBLE

Following confirmation of the command, the system automatically returns to the initial screen.

COMMAND INVALID

CONFIGURATION

if a "Soft Tunor" session is in

 

 

 

COMMAND INVALID

 

progress (initiated by after-sales

 

 

support technicians), pressing the "I/O"

 

SOFT TUNOR

 

button produces the message:

 

 

 

 

 

Language, display contrast and buzzer volume settings

These settings may be accessed by pressing the "settings" button.

Display of the settings selection screens

The series of screens in the figure opposite is displayed.

LANGUAGE = ENGLISH

*=CONFIRM.

*

DISPLAY CONTRAST >=SELECT *=CONFIRM.

*

BUZZER VOLUME >=SELECT *=CONFIRM.

*

Direct access to the function by pressing the "settings" button.

Selection of the display language: English, French, German, Italian, Spanish, Dutch, Swedish, Finnish, Portuguese.

This screen is a prompt to set the display contrast by successively pressing the ">" button. When the setting is confirmed by pressing the "*" button, the system goes on to the buzzer.

When this screen is displayed, the buzzer automatically turns on. Press the ">" button several times to adjust the volume. After confirmation of the buzzer volume by the "*" button, the system automatically returns to the initial screen.

initial screen

6739380EN/JC - Page 45

Page 45
Image 45
APC 6739380EN/JC user manual Inverter On/Off commands, Language, display contrast and buzzer volume settings