Environment information (cont.)

Signal transmission

These signals are each transmitted by two volt-free changeover contacts with a maximum breaking capacity of 5A 250V.

"overload" signal indicates that an overload has taken place (Pload > Pnominal in kVA);

"rectifier/charger function fault" signal indicates that:

a fault has taken place in the rectifier/charger module,

Mains 1 input switch Q1 is open;

"inverter function fault" signal indicates that a fault has taken place in the inverter module;

"transfer to inverter fault" signal indicates that the load transfer conditions from Mains 2 to the inverter are incorrect;

"transfer to Mains 2 fault" signal indicates that the transfer to Mains 2 conditions (voltage, frequency or phase) are incorrect and a forced transfer will result in a 0.8 second interruption in the supply of power to the load;

"rectifier/charger on" signal indicates the status of the module.

Note:

A Static Switch Cubicle receives only the following signals:

overload,

transfer to inverter fault,

transfer to Mains 2 fault.

Page 30 - 6739380EN/JC

Page 30
Image 30
APC user manual 30 6739380EN/JC