Configuring the Interface Expander

Shutdown

To configure the Interface Expander, you must choose one

modes

of the three available modes of automatic UPS shutdown.

 

Each shutdown mode is described in this section.

 

Confirmed

 

Until Low Battery

 

Timer

 

 

 

DIP switches: Select the shutdown mode by using the DIP switches as

Table 5described in the following table. (An abbreviated form of his table also appears on the bottom side of the Interface Expander circuit board.)

 

 

Switch Setting (=0, =1)

Shutdown Mode

 

 

 

 

1

2

3

4

 

 

 

 

 

 

 

Confirmed

0

0

0

*

 

 

 

 

 

Until Low Battery

0

0

1

N/A

 

 

 

 

 

 

 

2 min.

0

1

0

N/A

 

 

 

 

 

 

 

5 min.

0

1

1

N/A

 

 

 

 

 

 

Timer

10 min.

1

0

0

N/A

 

 

 

 

 

15 min.

1

0

1

N/A

 

 

 

 

 

 

 

 

30 min.

1

1

0

N/A

 

 

 

 

 

 

 

60 min.

1

1

1

N/A

 

 

 

 

 

 

 

Await

0

0

0

0

* Server on

Confirmation

 

 

 

 

 

 

 

 

 

Advanced Port

Treat as

0

0

0

1

 

 

Confirmed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Continued on next page

19