APC AP9607 Expander allows the UPS to run on battery until utility, Force the UPS to cycle power

Models: AP9607

1 42
Download 42 pages 63.46 Kb
Page 26
Image 26

Configuring the Interface Expander continued

Until Low

Until Low Battery shutdown mode is similar to the standard

Battery

operation of the UPS. During a utility failure, the Interface

shutdown mode

Expander allows the UPS to run on battery until utility

 

power is restored, or until the battery is exhausted. If the

 

Interface Expander detects a UPS Low Battery condition, it

 

sends a Low Battery signal on all ports for a period of time

 

equal to the Low Battery Signal Time and then shuts down

 

the UPS.

 

If utility power returns after the Low Battery timer has

 

begun, the Interface Expander will continue the countdown

 

and force the UPS to cycle power.

 

This mode is useful for applications which require maxi-

 

mum run time.

 

 

Timer shutdown

In Timer shutdown mode, the Interface Expander allows the

mode

UPS to operate on battery for a user-specified length of time

 

before shutting down the UPS. See “DIP switches: Table 5”

 

on page 19 for the available timer settings.

 

If power returns before the timer has run out, the Interface

 

Expander returns to On Line status. When the timer runs out

 

or when the Interface Expander detects a Low Battery con-

 

dition in the UPS, the Interface Expander sends a Low

 

Battery signal for a period of time equal to the Low battery

 

signal time and then shuts down the UPS.

 

Note: If you are using PowerChute software, set the shut-

 

down delay for a time longer than the Interface

 

Expander timer setting. Otherwise, if the power

 

returns after the server shuts down, the server may

 

not restart. To set the shutdown delay, go to Configu-

 

rationEvent Actions and select UPS On Battery

 

from the Event list and Shut Down Server in the

 

Action box. Click Options and enter a setting for

 

Begin Shutdown Sequence in __ Seconds. Click OK.

 

 

 

Continued on next page

22

Page 26
Image 26
APC AP9607 manual Expander allows the UPS to run on battery until utility, Force the UPS to cycle power, Mum run time