APC AP9607 If power returns before any connected server has signaled, Returns to On Line status

Models: AP9607

1 42
Download 42 pages 63.46 Kb
Page 25
Image 25

Configuring the Interface Expander continued

Behavior of

If power returns before any connected server has signaled

Confirmed mode

shutdown of the operating system, the Interface Expander

 

returns to On Line status.

 

If the Interface Expander detects a Low Battery condition in

 

the UPS before all connected servers have signaled shut-

 

down of the operating system, it notifies the servers that the

 

UPS battery is exhausted, shutting down the UPS after the

 

Low Battery Signal Time has elapsed.

 

If utility power returns after at least one server has con-

 

firmed shutdown of the operating system, but before all

 

servers have confirmed system shutdown, the Interface

 

Expander forces On Battery and Low Battery signals so that

 

the remaining servers shut down as well. The Interface

 

Expander sends the forced Low Battery signal for a period

 

of time equal to the Low Battery Signal Time and then shuts

 

down the UPS, which cycles power to restart the servers.

 

 

Confirmed

If you configure the Interface Expander in Confirmed shut-

shutdown mode

down mode by setting DIP switches 1, 2, and 3 in the down

and the

(0) position, you must set DIP switch #4 to determine the

Advanced port

behavior of the server or device connected to the Advanced

 

port.

 

When the Interface Expander is configured for Confirmed

 

mode, DIP switch #4 behaves as follows:

 

• With DIP switch #4 in the 0 (down) position, the

 

Advanced port operates normally, awaiting shutdown

 

confirmation in the Confirmed shutdown mode.

 

• With DIP switch #4 in the 1 (up) position, the Inter-

 

face Expander treats the Advanced port as always

 

confirmed. Use this setting when the Advanced port

 

will not be receiving a shutdown confirmation signal.

 

Note:When the shutdown mode of the Interface Expander is

 

set to Until Low Battery or Timer, the position of DIP switch

 

#4 has no effect.

Continued on next page

Page 25
Image 25
APC AP9607 manual If power returns before any connected server has signaled, Returns to On Line status, Port