Alarms and Events

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 5: Possible Alarms

 

 

 

 

 

 

 

TSM 3 temp.

Inverter module 3 has shut down

Find the vents for the UPS fans

 

 

shutdown

because the temperature on the

and check to see if the fans are

 

 

 

heat-sink is higher than the

operating. Do not try to open the

 

 

 

shutdown level. If bypass is within

unit, and do not insert anything

 

 

 

tolerance, the unit transfers to

into a fan vent. If the fans are not

 

 

 

static bypass operation.

operating, call APC Global

 

 

 

If not, the unit transfers to stand-

Service.

 

 

 

by and does not supply output

If the fans are operating, make

 

 

 

voltage.

sure the room temperature is

 

 

 

 

below 80° F (27° C). If not, cool

 

 

 

 

down the room. if the room was

 

 

 

 

already below this temperature,

 

 

 

 

call APC Global Service.

 

 

 

 

 

 

 

TSM 3 temp.

The temperature on the heat-sink

Find the vents for the UPS fans

 

 

warning

for inverter module 3 is higher than

and check to see if the fans are

 

 

 

the warning setting. The unit’s

operating. Do not try to open the

 

 

 

status does not change. However, if

unit, and do not insert anything

 

 

 

the temperature continues to rise,

into a fan vent. If the fans are not

 

 

 

the unit will sound a “TSM 3 temp.

operating, call APC Global

 

 

 

shutdown” alarm.

Service.

 

 

 

 

If the fans are operating, make

 

 

 

 

sure the room temperature is

 

 

 

 

below 80° F (27° C). If not, cool

 

 

 

 

down the room. if the room was

 

 

 

 

already below this temperature,

 

 

 

 

call APC Global Service.

 

 

 

 

 

 