|
|
| Alarms and Events |
|
|
|
|
|
|
|
|
|
|
|
|
| Table 5: Possible Alarms |
| |
|
|
|
|
|
| Mains is out of | The utility (AC input) voltage is too | If possible, restore AC input |
|
| tolerance (This | high or too low, so the unit | power to the UPS. If AC input is |
|
| alarm occurs | transfers to battery operation. If | available to the UPS, ask an |
|
| during a power | AC input returns to normal, the | electrician to make sure that 1) |
|
| outage) | unit transfers back to normal | the correct input voltage is |
|
|
| operation. If not, the unit continues | available to the UPS, and 2) this |
|
|
| to run on battery until the “Low DC | voltage is within a range the UPS |
|
|
| shutdown” alarm occurs. Then, if | will accept. |
|
|
| bypass voltage is within the range |
|
|
|
| programmed into the UPS, the unit |
|
|
|
| transfers to bypass. If not, the unit |
|
|
|
| transfers to |
|
|
|
| supply output voltage. |
|
|
|
|
|
|
|
| OFF Button | A user pushed the red “Off” button | Restart the unit by pressing the |
|
| Pushed (If the | or activated an emergency power | green button inside the door. If |
|
| alarm was | off shutdown. The unit switches to | the unit will not restart, the |
|
| caused by the | alarm was caused by an |
| |
| Off button, it is | output voltage. | emergency power off (EPO) |
|
| in the events |
| shutdown. Find out why this |
|
| log) |
| shutdown was activated and |
|
|
|
| make sure the emergency |
|
|
|
| situation has passed; then, |
|
|
|
| restart the unit by deactivating |
|
|
|
| the emergency power off |
|
|
|
| shutdown. |
|
|
|
|
|
|
| Output freq. is | The output frequency is too high, | Ask an electrician to make sure |
|
| out of tolerance | low, or unstable (out of tolerance). | that the correct input frequency is |
|
|
| The unit transfers to battery | being supplied to the UPS. Then, |
|
|
| operation and runs on battery until | call APC Global Service. |
|
|
| the “Low DC shutdown” alarm |
|
|
|
| occurs. Then, the unit transfers to |
|
|
|
| bypass if bypass is within |
|
|
|
| tolerance. If not, the unit transfers |
|
|
|
| to |
|
|
|
| output voltage. |
|
|
|
|
|
|
|
| Output is | The output voltage was | If other alarms are also active, |
|
| moment. out of | momentarily too high or too low | troubleshoot these alarms first. If |
|
| tolerance | (out of tolerance). If bypass is | this is the only alarm, call APC |
|
|
| within tolerance, the unit transfers | Global Service. |
|
|
| to static bypass operation. If not, |
|
|
|
| the unit transfers to |
|
|
|
| does not supply output voltage. |
|
|
|
|
|
|
|
18 | User Guide APC BC300 Series 40kW 208/450/480V UPS |