Altivar® 58 TRX AC Drives

Wiring Recommendations

Wiring Diagram for ATV58 TRX Type E Controllers (Single Phase)

L1

 

 

 

 

 

 

F1

 

 

 

 

F2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2

(1) Line Reactor

(3)

1 Phase Type E.eps

 

 

 

(2)

(4)

AO1 COM

 

 

 

 

 

 

 

 

 

L1

L2

R1A

R1C

R1B

K13 K14

AI1 +10

AI2

+24

0 Fw

LI1

LI2

LI3

LI4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

3

 

 

 

 

 

 

 

Fault

Drive

(6)

Manual

 

 

 

 

 

 

 

 

 

 

 

 

 

Run

 

Speed

 

1

 

1

(6)

 

 

 

 

 

 

 

 

 

Potentiometer

 

 

 

 

 

O

Fw

U

V

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ATV58E

 

 

ATV58E

 

 

1

[7] Stop

 

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

U09M2ZU

 

 

3

Stop

 

 

 

 

 

Other Models

 

 

 

 

 

 

 

 

 

 

 

and U18M2ZU

 

 

 

 

Fwd

 

 

 

 

 

 

PB

 

 

 

 

 

 

 

 

 

 

 

 

PA

 

 

+

-

 

 

 

 

 

T1

T2

T3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

Brake

(5)

 

 

 

 

 

 

 

 

 

 

 

3φ

 

Resistor

 

 

 

+

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brake

 

 

 

(5)

 

 

 

 

 

 

 

 

 

 

Module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PA

PB

 

 

 

 

 

Brake

Resistor

Notes

1.Line reactor, if required.

2.Fault relay contacts for remote signalling of the drive controller state. Contact state is shown with the drive controller de-energized or faulted.

3.Internal +24 V. When using a +24 Vdc external supply, connect the 0 V to the COM terminal. Do not use the +24 V terminal on the control board, but connect logic inputs to external +24 V.

4.Auxiliary on output contactor. If the controller is re-programmed, the R2 function must be assigned to Output Contactor Command.

5.Use dynamic braking module VW3A58701 with drive controllers ATV58EU09M2ZU and U18M2ZU if dynamic braking is required. See pages 34–37 for the available braking resistor kits.

6.Manual speed potentiometer and three-position switch are factory-installed in the terminal block cover. There is enough space in the terminal block cover to install two more 16-mm operators.

7.When user-installed wiring is added from terminals +24 to LI2 and when the drive controller programming is at the factory settings, placing the selector switch in this position will command the controller to run in reverse. The function of LI2 can be altered with the programming options. See page 50 for the functions to which LI2 may be assigned.

109

09/2003

 

© 2000–2003 Schneider Electric All Rights Reserved

 

 

 

 

Page 109