Altivar® 58 TRX AC Drives

EMC Kits and RFI Filters

ELECTROMAGNETIC COMPATIBILITY (EMC) KITS

ATV58 TRX drive controllers are marked with the CE European Community mark.

The ATV58 TRX drive controller is considered to be a component. It is neither a machine nor a piece of equipment ready for use in accordance with the European Community directives (machinery directive or electromagnetic compatibility directive). It is the user’s responsibility to ensure that the machine meets these standards.

Metal EMC plate kits are available for ATV58 TRX drive controllers to assist in meeting the European Community EMC directives. The plate is used for landing the shield of the shielded cable. These kits are for integrators and end-users who are including the drive controller as part of a machine to be exported to Europe requiring compliance to these directives. When installed as directed in Instruction Bulletin 30072-450-04 (shipped with the kit), the requirements of EMC Directive Level A will be met. To achieve Level B compliance, install an external RFI filter (see the following sections). See page 125 for EMC kit dimensions.

EMC Kit Catalog Numbers

For Drive Controllers

EMC Kit Catalog

Number

 

 

 

ATV58•U09M2, ATV58•U18M2

VW3A58831

 

 

ATV58•U29M2, ATV58•U41M2, ATV58•U18N4, ATV58•U29N4, ATV58•U41N4

VW3A58832

 

 

ATV58U54M2, ATV58U72M2, ATV58U54N4, ATV58U72N4, ATV58U90N4

VW3A58833

 

 

ATV58U90M2, ATV58D12M2, ATV58D12N4, ATV58D16N4, ATV58D23N4

VW3A58834

 

 

INTERNAL RFI FILTERS

The ATV58 TRX drive controller can be supplied with internal radio interference suppression input filters to comply with the EMC “products” standards IEC 61800-3 and EN 61800-3 concerning variable speed controllers. Compliance with these standards meets the requirements of the European directive on EMC.

The following ATV58 TRX controllers are available without input filters for use in situations where EMC conformity is not necessary:

ATV58HU54N4 to ATV58HD79N4 drive controllers are available with or without integrated input filters. If the catalog number includes an “X”, the drive controller does not have an integrated input filter.

ATV58HD16M2X to ATV58HD46M2X drive controllers are not available with integrated input filters.

The following ATV58 TRX drive controllers are always supplied with integrated input filters:

ATV58U09M2 to ATV58D12M2 drive controllers; and

ATV58U18N4 to ATV58U41N4 drive controllers.

EXTERNAL RFI FILTERS

External RFI input filters are available to meet the strictest requirements. These filters are designed to reduce conducted emissions on the mains supply to below the limits of standards EN 55022 class B or EN 55011 class A. The motor cable must be longer than 5 m (16 feet) for ATV58•U09M2 to ATV58•D12M2 and ATV58•U18N4 to ATV58•D23N4 controllers, or 25 m (82 feet) for ATV58HD28N4 to ATV58HD79N4 controllers.

External RFI filters are mounted beneath ATV58 TRX Type H controllers. They have tapped holes for mounting the drive controller which they support. The filters are mounted to the side of ATV58 TRX Type E controllers.

Because the filter needs a direct path to ground to work properly, RFI filters can only be used on wiring systems with a neutral connected directly to ground. Do not use RFI filters on wiring systems grounded through a high impedance or on systems with an isolated (floating) neutral.

38

© 2000–2003 Schneider Electric All Rights Reserved

 

09/2003

 

 

 

 

Page 38
Image 38
Schneider Electric 58 TRX manual EMC Kits and RFI Filters, Electromagnetic Compatibility EMC Kits, Internal RFI Filters