[1]Fast-acting or time delay Class J fuses are acceptable. Class T fuses are acceptable. Class CC fuses may be used if recommended fuse rating is 30 A or lower.

[2]Fast-acting Class J fuses. Class T fuses are acceptable.

[1]Fast-acting or time delay Class J fuses are acceptable. Class T fuses are acceptable. Class CC fuses may be used if recommended fuse rating is 30 A or lower.

[2]Fast-acting Class J fuses. Class T fuses are acceptable.

CT

Constant Torque

CTLN

Constant Torque Low

 

Noise

VTLN

Variable Torque Low

 

Noise

VT

Variable Torque

 

 

Altivar® 58 TRX AC Drives

Wiring Recommendations

Recommended Branch Circuit Protection Devices

Branch circuit protection must be installed on the input (line side) of the drive controllers. Input fuses may be used on 1/2 hp to 500 hp drive controllers; circuit breakers may be used on 1/2 hp to 100 hp drive controllers.

Fuses

The fuses specified in Tables 1–3 (pages 113–114) are suitable for branch short circuit protection and provide excellent short circuit protection for the drive. Fuses are recommended for ATV58 TRX Type H and Type FVC drives when they are wall mounted.

Circuit Breakers

Circuit breakers will also provide branch short circuit protection. Because circuit breakers are typically slower than fuses, they are not as effective in limiting damage to the controller in the event of an internal drive short circuit such as shorted bus connections, shorted input rectifier, or failure of the internal solid state overcurrent protection circuit in the controller. Refer to the ALTIVAR 58 TRX Installation Guide for Type H Controllers (VVDED397048US) for recommended circuit breakers and application considerations.

Table 1: Recommended Fuses: 208/230 V Single-Phase Drive Controllers

 

Motor

Drive Controller

F1-F2

 

Line Power Fuses

 

 

 

 

hp

 

kW

ATV58H•••••

Class J

 

 

 

 

 

 

0.5

 

0.37

U09M2

10 [1]

1

 

0.75

U18M2

15 [1]

2

 

1.5

U29M2

30 [1]

3

 

2.2

U41M2

30 [1]

4

 

3

U72M2

35 [1]

5

 

4

U90M2

60 [1]

7.5

 

5.5

D12M2

70 [1]

10

 

7.5

D16M2

90 [2]

15

 

11

D23M2

125 [2]

20

 

15

D28M2

150 [2]

25

 

18.5

D33M2

175 [2]

30

 

22

D46M2

200 [2]

Table 2: Recommended Fuses: 208/230 V Three-Phase Drive Controllers

 

Motor

Drive Controller

 

F1-F2-F3

 

 

 

 

 

Line Power Fuses

 

 

 

 

 

 

 

 

 

 

 

 

hp

 

kW

ATV58H•••••

 

Class J [1]

 

 

 

 

 

 

 

 

2

 

1.5

U29M2

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

2.2

U41M2

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

U54M2

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

4

U72M2

 

 

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5

 

5.5

U90M2

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

7.5

D12M2

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CT, VTLN

F1-F2-

 

VT

 

 

 

 

CTLN

F1-F2-F3

F3

 

F1-F2-F3

hp

 

kW

ATV58H••

ATV58H••

 

ATV58H•••••

Class J [2]

Class J

Class J [2]

 

 

 

 

 

 

•••

[2]

 

•••

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

7.5

D16M2

70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

11

D23M2

90

D16M2

70

D16M2

70

 

 

 

 

 

 

 

 

 

20

 

15

D28M2

110

D23M2

90

D16M2

90

 

 

 

 

 

 

 

 

 

25

 

18.5

D33M2

125

D28M2

110

D23M2

125

 

 

 

 

 

 

 

 

 

30

 

22

D46M2

175

D33M2

125

D28M2

150

 

 

 

 

 

 

 

 

 

 

40

 

30

 

 

 

D46M2

175

D33M2

175

 

 

 

 

 

 

 

 

 

 

50

 

37

 

 

 

 

 

D46M2

200

 

 

 

 

 

 

 

 

 

 

 

113

09/2003

 

© 2000–2003 Schneider Electric All Rights Reserved

 

 

 

 

Page 113
Image 113