Class 8839 Econoflex™ AC Drives
Ratings
195
09/2003 © 2000–2003 Schneider Electric All Rights Reserved
CONTROLLER RATINGS (CONTINUED)INPUT CURRENT RATINGS

Class 8839 ATV58 Econoflex Drive Controller Ratings 208 Vac

Drive Controller
Catalog NumberMotor Power
208 Vac 60 Hz (HP) Maximum Continuous
Output Current (A)Max. Transient (60 s)
Output Current (A) Power Converte r
Part Number
58EC•2V_ 1 4.6 5.1 FLEX58U29M2
58ED•2V_ 2 7.5 8.3 FLEX58U29M2
58EE•2V_ 3 10.6 11.7 FLEX58U41M2
58EF•2V_ 5 16.7 18.4 FLEX58U72M2
58EG•2V_ 7.5 24.2 26.6 FLEX58U90M2
58EH•2V_ 10 30.8 33.9 FLEX58D12M2
58EJ•2V_ 15 46.2 50.8 FLEX58D16M2
58EK•2V_ 20 59.4 65.3 FLEX58D16M2
58EL•2V_ 25 74.8 82.3 FLEX58D23M2
58EM•2V_ 30 88 96.8 FLEX58D28M2
58EN•2V_ 40 114 125.4 FLEX58D33M2
58EP•2V_ 50 143 157.3 FLEX58D46M2
The • may be A or G; A denotes a Type 12K enclosure, G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
Power shown is for a carrier switching frequency of 8 kHz. For a switching frequency between 12 and 1 6kHz, select the next largest size drive
controller. If the duty cycle does not exceed 60% (36 s maximum for a 60 s cycle), this is not necessary.
Continuous output current based on NEC table 430-150. The Econoflex controller nameplate rating is per the NEC table, not the current v alue listed
in the keypad lookup table.
Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 460 Vac
Drive Controller
Catalog Number
Motor Power
460 Vac 60 Hz
(HP)
5 kAIC (0.141 mH)
10 kAIC (0.070 mH)
(A)
22 kAIC
(0.032 mH)
(A)
Factory-mounted Line Reactor
Mod A09
5 kAIC (0.141 mH)
10 kAIC (0.070 mH)
(A)
22 kAIC
(0.032 mH)
(A)
58EC•4V_ 1 2.8 3.2 1.8 2
58ED•4V_ 2 4.8 5.2 3.5 3.8
58EE•4V_ 3 6.5 7.6 4.9 5.7
58EF•4V_ 5 10.7 12.6 7.9 9.3
58EG•4V_ 7.5 14.3 16.9 11.5 13.2
58EH•4V_ 10 18.2 22 12.9 15.6
58EJ•4V_ 15 25.3 30 .3 22.9 22.9
58EK•4V_ 20 32 38.4 25.2 30
58EL•4V_ 25 32.7 34.1 32. 7 34.1
58EM•4V_ 30 38.1 39.8 38.1 39.8
58EN•4V_ 40 49.3 51.6 49.3 51.6
58EP•4V_ 50 61.8 65.4 61.8 65.4
58EQ•4V_ 60 75.277.7 75.277.7
58ER•4V_ 75 96.3100.8 96.3100.8
58ES•4V_ 100 122.6129.3 122.6129.3
Select conductor based on NEC.
The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number
continues. See page 186 for detailed description of catalog numbers.
Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers.
10 kAIC.