Class 8839 Econoflex™ AC Drives

Ratings

CONTROLLER RATINGS (CONTINUED)

Class 8839 ATV58 Econoflex Drive Controller Ratings 208 Vac

Drive Controller

Motor Power

Maximum Continuous

Max. Transient (60 s)

Power Converter

Catalog Number

208 Vac 60 Hz (HP)

Output Current (A)

Output Current (A)

Part Number

58EC•2V_

1

4.6

5.1

FLEX58U29M2

 

 

 

 

 

58ED•2V_

2

7.5

8.3

FLEX58U29M2

 

 

 

 

 

58EE•2V_

3

10.6

11.7

FLEX58U41M2

 

 

 

 

 

58EF•2V_

5

16.7

18.4

FLEX58U72M2

 

 

 

 

 

58EG•2V_

7.5

24.2

26.6

FLEX58U90M2

 

 

 

 

 

58EH•2V_

10

30.8

33.9

FLEX58D12M2

 

 

 

 

 

58EJ•2V_

15

46.2

50.8

FLEX58D16M2

 

 

 

 

 

58EK•2V_

20

59.4

65.3

FLEX58D16M2

 

 

 

 

 

58EL•2V_

25

74.8

82.3

FLEX58D23M2

 

 

 

 

 

58EM•2V_

30

88

96.8

FLEX58D28M2

 

 

 

 

 

58EN•2V_

40

114

125.4

FLEX58D33M2

 

 

 

 

 

58EP•2V_

50

143

157.3

FLEX58D46M2

 

 

 

 

 

The • may be A or G; A denotes a Type 12K enclosure, G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number continues. See page 186 for detailed description of catalog numbers.

Power shown is for a carrier switching frequency of 8 kHz. For a switching frequency between 12 and 1 6kHz, select the next largest size drive

controller. If the duty cycle does not exceed 60% (36 s maximum for a 60 s cycle), this is not necessary.

Continuous output current based on NEC table 430-150. The Econoflex controller nameplate rating is per the NEC table, not the current value listed in the keypad lookup table.

INPUT CURRENT RATINGS

Input Line Currents for Selection of Branch Circuit Feeder for Class 8839 Econoflex 460 Vac

 

 

 

 

 

Factory-mounted Line Reactor

Drive Controller

Motor Power

5 kAIC (0.141 mH)

22 kAIC

Mod A09

 

460 Vac 60 Hz

10 kAIC (0.070 mH)

(0.032 mH)

5 kAIC (0.141 mH)

22 kAIC

Catalog Number

(HP)

(A)

 

(A)

 

 

10 kAIC (0.070 mH)

(0.032 mH)

 

 

 

 

 

 

 

 

 

 

(A)

(A)

 

 

 

 

 

 

 

58EC•4V_

1

2.8

 

3.2

1.8

2

 

 

 

 

 

 

 

58ED•4V_

2

4.8

 

5.2

3.5

3.8

 

 

 

 

 

 

 

58EE•4V_

3

6.5

 

7.6

4.9

5.7

 

 

 

 

 

 

 

58EF•4V_

5

10.7

 

12.6

7.9

9.3

 

 

 

 

 

 

 

58EG•4V_

7.5

14.3

 

16.9

11.5

13.2

 

 

 

 

 

 

 

58EH•4V_

10

18.2

 

22

12.9

15.6

 

 

 

 

 

 

 

58EJ•4V_

15

25.3

 

30.3

22.9

22.9

 

 

 

 

 

 

 

58EK•4V_

20

32

 

38.4

25.2

30

 

 

 

 

 

 

 

58EL•4V_

25

32.7

 

34.1

32.7

34.1

 

 

 

 

 

 

 

58EM•4V_

30

38.1

 

39.8

38.1

39.8

 

 

 

 

 

 

 

58EN•4V_

40

49.3

 

51.6

49.3

51.6

 

 

 

 

 

 

 

58EP•4V_

50

61.8

 

65.4

61.8

65.4

 

 

 

 

 

 

 

58EQ•4V_

60

75.2

77.7

75.2

77.7

58ER•4V_

75

96.3

100.8

96.3

100.8

58ES•4V_

100

122.6

129.3

122.6

129.3

Select conductor based on NEC.

The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number continues. See page 186 for detailed description of catalog numbers.

Factory modification A09 is optional for 1 to 20 HP controllers and included in 25 to 100 HP controllers. 10 kAIC.

09/2003

195

© 2000–2003 Schneider Electric All Rights Reserved

Page 195
Image 195
Schneider Electric 58 TRX manual Input Current Ratings, Class 8839 ATV58 Econoflex Drive Controller Ratings 208 Vac, 195