Class 8839 58M Enclosed AC Drives

Three Phase Line Reactors

The Class 8839 58M Enclosed AC Drives are designed to operate from industrial power systems with normal AC line conditions without the need of additional line impedance from either an isolation transformer or a line reactor. However, when abnormal line conditions exist, additional line impedance may be required. Typically, line reactors are used to:

Reduce the input rms current to the AC drive ratings

Lower the available fault current on high fault distribution systems

Limit the total harmonic voltage distortion from the AC drive at the point of common coupling to align with IEEE 519 guidelines

Prevent AC drive nuisance tripping due to transient overvoltages from power factor correction capacitor switching

HP Rating

208/230 VAC Line Reactor

460 VAC Line Reactor

Enclosed Standard Option

Part No. (Integrated)

Part No. (Integrated)

 

 

 

 

 

 

1

RL–01202

RL–00802

A10

 

 

 

 

2

RL–01202

RL–00802

A10

 

 

 

 

3

RL–01202

RL–00802

A10

 

 

 

 

5

RL–01801

RL–01203

A10

 

 

 

 

7.5

RL–01801

RL–01203

A10

 

 

 

 

10

RL–03501

RL–01802

A10

 

 

 

 

15

RL–03501

RL–01802

A10

 

 

 

 

20

RL–08001

RL–01802

A10

 

 

 

 

25

RL–08001

RL–03502

A10

 

 

 

 

30

RL–10001

RL–03502

A10

 

 

 

 

40

RL–10001

RL–03502

A10

 

 

 

 

50

RL–16002

RL–08002

A10

 

 

 

 

60

RL–08002

A10

 

 

 

 

75

RL–10002

A10

 

 

 

 

100

RL–13002

A10

 

 

 

 

125

RL–16013

A10

 

 

 

 

150

RL–20013

A10

 

 

 

 

200

RL–25013

A10

 

 

 

 

250

RL–32013

A10

 

 

 

 

300

RL–40013

A10

 

 

 

 

350

RL–50013

A10

 

 

 

 

400

RL–50013

A10

 

 

 

 

450

RL-60013

A10

 

 

 

 

500

RL-60013

A10

 

 

 

 

Line

Load

LineLoad.eps

B1

B2

A1

A2

 

C1

C2

 

Line Reactors:

1.The line reactors are manufactured by MTE, Inc.

2.Harmonic compensated up to 150% of nominal current ratings

3.5% nominal reactance

4.Refer to the following publications on the subject of harmonics and benefits of drive isolation transformers:

8803PD9402–Power Systems Harmonics– Cause and Effects of AC Drives.

7460HO9501–Drive Isolation Transformers-Application, Selection and Specification Data

7460PD9501– Drive Isolation Transformers–Solutions to Power Quality