Class 8839 58M Enclosed AC Drives
Three Phase Line Reactors
The Class 8839 58M Enclosed AC Drives are designed to operate from industrial power systems with normal AC line conditions without the need of additional line impedance from either an isolation transformer or a line reactor. However, when abnormal line conditions exist, additional line impedance may be required. Typically, line reactors are used to:
•Reduce the input rms current to the AC drive ratings
•Lower the available fault current on high fault distribution systems
•Limit the total harmonic voltage distortion from the AC drive at the point of common coupling to align with IEEE 519 guidelines
•Prevent AC drive nuisance tripping due to transient overvoltages from power factor correction capacitor switching
HP Rating | 208/230 VAC Line Reactor | 460 VAC Line Reactor | Enclosed Standard Option | |
Part No. (Integrated) | Part No. (Integrated) | |||
|
| |||
|
|
|
| |
1 | A10 | |||
|
|
|
| |
2 | A10 | |||
|
|
|
| |
3 | A10 | |||
|
|
|
| |
5 | A10 | |||
|
|
|
| |
7.5 | A10 | |||
|
|
|
| |
10 | A10 | |||
|
|
|
| |
15 | A10 | |||
|
|
|
| |
20 | A10 | |||
|
|
|
| |
25 | A10 | |||
|
|
|
| |
30 | A10 | |||
|
|
|
| |
40 | A10 | |||
|
|
|
| |
50 | A10 | |||
|
|
|
| |
60 | – | A10 | ||
|
|
|
| |
75 | – | A10 | ||
|
|
|
| |
100 | – | A10 | ||
|
|
|
| |
125 | – | A10 | ||
|
|
|
| |
150 | – | A10 | ||
|
|
|
| |
200 | – | A10 | ||
|
|
|
| |
250 | – | A10 | ||
|
|
|
| |
300 | – | A10 | ||
|
|
|
| |
350 | – | A10 | ||
|
|
|
| |
400 | – | A10 | ||
|
|
|
| |
450 | – | A10 | ||
|
|
|
| |
500 | – | A10 | ||
|
|
|
|
Line | Load | LineLoad.eps |
B1 | B2 | |
A1 | A2 |
|
C1 | C2 |
|
Line Reactors:
1.The line reactors are manufactured by MTE, Inc.
2.Harmonic compensated up to 150% of nominal current ratings
3.5% nominal reactance
4.Refer to the following publications on the subject of harmonics and benefits of drive isolation transformers:
—
—
—7460PD9501– Drive Isolation