Altivar® 58 TRX AC Drives

Line Reactors and Output Filters

Wiring systems with a neutral connected directly to ground can be classified in two ways, as TT or TN.

1.TT indicates a neutral wire connected directly to ground. The exposed conductive parts of the product are connected to ground via a separate path.

2.TN indicates a neutral wire connected directly to ground and the exposed conductive parts of the product are connected to ground via the same path.

Wiring systems grounded through a high impedance or systems with an isolated (floating) neutral can be referred to as IT. Standard IEC 1800-3, appendix D2.1, states that filters must not be used with IT mains supplies because they prevent the ground leakage detectors from working reliably. In addition, the effectiveness of the filters on IT mains supplies depends on the type of impedance between neutral and earth, and is therefore not recommended.

In the case of a machine which must be installed on an IT supply, the solution is to insert an isolation transformer and operate the machine locally using a TN or TT supply.

Characteristics

Conformity to standards

 

EN 133200

 

 

 

Degree of protection

 

IP 21 and IP 41 on upper part

 

 

 

Maximum relative

 

93% with no condensation or dripping water, conforming to IEC 68-2-3

humidity

 

 

 

 

 

 

Ambient air temperature

Operation

–10 to 60 °C (14 to 140 °F)

 

 

Storage

–25 to 70 °C (–13 to 158 °F)

 

 

 

 

Operating altitude

Up to 1000 m (3280 feet)

No derating required

 

 

Above 1000 m (3280 feet)

Derate the current by 1% for each additional 100 m (328 feet)

 

 

 

 

Maximum nominal voltage

50/60 Hz single-phase

240 Vac +10%

 

 

50/60 Hz 3-phase

500 Vac +10%

 

 

 

 

Refer to page 125 for dimensions and to page 132 for selection.

LINE REACTORS

Line reactors can improve protection against line overvoltage surges and reduce input currents to the drive controller by adding impedance. The additional impedance also reduces the harmonic current distortion produced by a typical 6-pulse diode rectifier used to convert AC to DC in most drive controllers. Additional impedance is recommended when the impedance of the power distribution system is low, such as when the power rating of the system transformer is ten times larger than the power rating of the drive controller. Single-phase line reactors are available for single-phase input rated ATV58 TRX Type H drive controllers. See pages 125, 132, and 133 for dimensions and selection.

MOTOR PROTECTING OUTPUT FILTERS

The motor protecting output filters combine inductance, capacitance, and resistance to form a low pass filter. They should be considered for use in applications where the wiring to the motor(s) is longer than 100 ft. (30.5 m). These filters lower the dv/dt levels to prevent exciting the natural resonant frequency of the output circuit (drive controller, motor cables, and motor). Motors compliant to NEMA MG1, Part 31 guidelines generally do not require the use of motor protecting filters. See page 133 for dimensions and selection.