Available Type H Models (Continued)

Input Line

Voltag e

3-Phase Motor Power (HP) Continuous Output Current (A) Catalog No.

without Keypad

CTCTLNVTVTLNCTCTLNVTVTLN

400/460 Vac
3-Phase 1 — 1 1 2.3 2.1 2.1 ATV58HU18N4ZU
2 — 2 2 4.1 — 3.4 3.4 ATV58HU29N4ZU
3 — 3 3 5.8 — 4.8 4.8 ATV58HU41N4ZU
———5
7.8 — 6.2 7.6ATV58HU54N4XZU
5—5*7.510.5 — 7.6*11ATV58HU72N4XZU
7.5 — 7.5*1013 — 11*14ATV58HU90N4XZU
10 — 10*1517.6 — 14*21ATV58HD12N4XZU
15 — 15*2024.2 — 21*27ATV58HD16N4XZU
20 — 20*2533 — 27*34ATV58HD23N4XZU
25 20 25/30 25 40.7 33 34/40 34 ATV58HD28N4XZU
30 25 40 30 48.4 40.7 52 40 ATV58HD33N4XZU
40 30 50 40 66 48.4 65 52 ATV58HD46N4XZU
50 40 60 50 79.2 66 77 65 ATV58HD54N4XZU
60 50 75 60 93.5 79.2 96 77 ATV58HD64N4XZU
75 60 100 75 115.5 93.5 124 96 ATV58HD79N4XZU
... ... 125 ... ... ... 156 ... ATV58HC10N4XZU
... ... 150 ... ... ... 180 ... ATV58HC13N4XZU
... ... 200 ... ... ... 240 ... ATV58HC15N4XZU
... ... 250 ... ... ... 302 ... ATV58HC19N4XZU
... ... 300 ... ... ... 361 ... ATV58HC23N4XZU
... ... 350 ... ... ... 414 ... ATV58HC25N4XZU
... ... 400 ... ... ... 477 ... ATV58HC28N4XZU
... ... 450 ... ... ... 515 ... ATV58HC31N4XZU
... ... 500 ... ... ... 590 ... ATV58HC33N4XZU
Abbreviations: CT = constant torque CTLN = constant torque, low noise; VT = variable torque; VTLN = variable torque, low noise.
If an EMC filter to meet level A compliance is desired, delete the X from the catalog number.
*These ratings encompass all 400/460 Vac applications with or without an EMC filter. For 460 Vac applications without an EMC filter, these ratings
would be the same as the ratings in the VTLN columns.
These products, without EMC filters, are for 460 Vac applications and can be used at the motor power and output current ratings provided in the
VTLN columns. For 400 Vac applications, or if an EMC filter is required, delete the X fr om the cat alog n um ber and use the motor power and output
current ratings provided in the CT and VT columns. Do not use the VTLN ratings denoted with the symbol.