Altivar® 58 TRX AC Drives
Type E Drive Controllers
ATV58NEMAb_w no back.tif
ATV58 TRX Type E Product Family
12
©
ATV58 TRX TYPE E DRIVE CONTROLLERS
The ATV58 TRX family of
•1 to 7½ hp (0.75 to 5.5 kW), 400/460 Vac,
•½ to 3 hp (0.37 to 2.2 kW), 200/240 Vac,
•2 to 3 hp (1.5 to 2.2 kW), 200/240 Vac,
Each ATV58 TRX Type E drive controller contains:
•A GV2 manual motor starter, ATV58 TRX drive controller, and an output contactor
•A
•A manual speed potentiometer mounted on the front of the enclosure
•Space for two additional
•Four conduit openings that are closed with plugs
•A transparent plastic door for viewing the status LEDs and a separately- supplied keypad
All ATV58 TRX communication and I/O options can be used in the Type E controllers. The Type E drive controllers can be used on constant or variable torque applications. The ratings are shown in the tables below.
200 Vac
Frame | Drive Controller | Motor Power▼ | Rated | Transient | ||
Output Current | ◆ | |||||
Size▲ | Catalog Number |
|
|
| Output Current | |
kW |
| HP | A | A | ||
|
|
| ||||
|
|
|
|
|
|
|
1 | ATV58EU09M2ZU |
| 0.37 | 0.5 | 2.3 | 3.1 |
|
|
|
|
|
|
|
1 | ATV58EU18M2ZU |
| 0.75 | 1 | 4.1 | 5.6 |
|
|
|
|
|
|
|
2 | ATV58EU29M2ZU |
| 1.5 | 2 | 7.8 | 10.6 |
|
|
|
|
|
|
|
3 | ATV58EU41M2ZU■ |
| 2.2 | 3 | 11 | 15 |
200 Vac | ||||||
|
|
|
|
|
|
|
Frame | Drive Controller | Motor Power▼ | Rated | Transient | ||
Output Current | ◆ | |||||
Size▲ | Catalog Number |
|
|
| Output Current | |
kW |
| HP | A | A | ||
|
|
| ||||
|
|
|
|
|
|
|
2 | ATV58EU29M2ZU |
| 1.5 | 2 | 7.8 | 10.6 |
|
|
|
|
|
|
|
3 | ATV58EU41M2ZU |
| 2.2 | 3 | 11 | 15 |
|
|
|
|
|
| |
400 Vac | ||||||
|
|
|
|
|
|
|
Frame | Drive Controller | Motor Power▼ | Rated | Transient | ||
Output Current | Output Current◆ | |||||
Size▲ | Catalog Number |
|
|
|
|
|
kW |
| HP | A | A | ||
|
|
| ||||
|
|
|
|
|
|
|
2 | ATV58EU18N4ZU |
| 0.75 | 1 | 2.3 | 3.1 |
|
|
|
|
|
|
|
2 | ATV58EU29N4ZU |
| 1.5 | 2 | 4.1 | 5.6 |
|
|
|
|
|
|
|
2 | ATV58EU41N4ZU |
| 2.2 | 3 | 5.8 | 7.9 |
|
|
|
|
|
|
|
3 | ATV58EU54N4ZU |
| 3 | – | 7.8 | 10.6 |
|
|
|
|
|
|
|
3 | ATV58EU72N4ZU |
| 4 | 5 | 10.5 | 14.3 |
|
|
|
|
|
|
|
3 | ATV58EU90N4ZU |
| 5.5 | 7.5 | 13 | 17.7 |
|
|
|
|
|
|
|
▲For dimensions, see page 122; for wiring diagrams, see pages 109 and 110.
▼Power indicated is for a switching frequency between 0.5 and 4 kHz, and at steady state. For switching frequency between 8 and 16 kHz, use the next largest size drive controller. (For example, for 2 hp, order drive controller ATV58EU41M2ZU.) If the duty cycle (that is, the drive controller run time) does not exceed 60% (36 second maximum for a 60 second cycle), this is not necessary.
◆For 60 seconds.
■A line reactor (3% minimum) must be used with this drive controller.
09/2003