Class 8839 Econoflex™ AC Drives
Dissipated Watts Loss
198 09/2003
© 2000–2003 Schneider Electric All Rights Reserved

DISSIPATED WATTS LOSS

The total dissipated watts loss is provided for sizing the en vironme nt HV A C co oling requirem ents based

upon worst-case conditions.

Total Dissipated Watts Loss for Econoflex 460 Vac Controllers

Drive Controller Catalog NumberHorsepower Total Dissipated Watts Loss
58EC•4V_ 1 185
58ED•4V_ 2 230
58EE•4V_ 3 252
58EF•4V_ 5 349
58EG•4V_ 7.5 438
58EH•4V_ 10 512
58EJ•4V_ 15 643
58EK•4V_ 20 766
58EL•4V_ 25 853
58EM•4V_ 30 975
58EN•4V_ 40 1133
58EP•4V_ 50 1251
58EQ•4V_ 60 1318
58ER•4V_ 75 1692
58ES•4V_ 100 1972

Total Dissipated Watts Loss for Econoflex 230 Vac Controllers

Drive Controller Catalog NumberHorsepower Total Dissipated Watts Loss
58EC•3V_ 1 237
58ED•3V_ 2 298
58EE•3V_ 3 380
58EF•3V_ 5 406
58EG•3V_ 7.5 510
58EH•3V_ 10 732
58EJ•3V_ 15 934
58EK•3V_ 20 1098
58EL•3V_ 25 1210
58EM•3V_ 30 1258
58EN•3V_ 40 1569
58EP•3V_ 50 1899

Total Dissipated Watts Loss for Econoflex 208 Vac Controllers

Drive Controller Catalog NumberHorsepower Total Dissipated Watts Loss
58EC•2V_ 1 238
58ED•2V_ 2 297
58EE•2V_ 3 384
58EF•2V_ 5 408
58EG•2V_ 7.5 513
58EH•2V_ 10 735
58EJ•2V_ 15 939
58EK•2V_ 20 1100
58EL•2V_ 25 1213
58EM•2V_ 30 1263
58EN•2V_ 40 1580
58EP•2V_ 50 1923
The • may be A or G; A denotes a Type 12K enclosure; G denotes a Type 1 enclosure. The underscore (_) indicates that the catalog number