Class 8839 Econoflex™ AC Drives
Drive Selection
186 09/2003
© 2000–2003 Schneider Electric All Rights Reserved
DRIVE SELECTION

Class 8839 Econoflexä enclosed drives are tailo red f or commerci al market sp ecification s for pu mp and f an applic ations. To select,

identify the catalog number by Class, Type, and Modification(s) numbers as shown below.

Class Type Number Modifications

8839 58E V

➀➁➂➃➄➅ ➇➈

Product

Code Enclosed Drive
58E Econoflex

Horsepower

Code Rating at 208,
230, 460 Vac
C1 HP
D2 HP
E3 HP
F5 HP
G 7.5 HP
H10 HP
J15 HP
K20 HP
L25 HP
M30 HP
N40 HP
P50 HP
Code Rating at
460 Vac
Q60 HP
R75 HP
S 100 HP

Enclosure Type

Code Environment
Rating
A Type 12K
G Type 1

Voltage Rating

Code Voltage
2208 Vac
3230 Vac
4460 Vac

Application Type

Code Torque
V Variable Torque

Device Type

Code Power Circuit
W Without Bypass
Y With Bypass[1]

Misc. Options

Code Feature
A09 Line Reactor[2]
B09 Line Contactor[3]
C09 3 to 15 PSI
Transducer[4]
D09 Omit Keypad[12]
E09 Smoke Purge[5]
G09 22 kAIC UL
Coordinated
Rating
H09 Analog Card,
0 to 20 mA
output[6]
J09 0 to 10 mA
Auto Speed
Reference[13]

Light Option

Code Light Cluster
A08 Power ON, AFC Run,
AFC Fault, Auto[7]
B08 Power ON, AFC Run,
AFC Fault, Bypass[7,8]
C08 Power ON, AFC Run,
AFC Fault[7,9]

Control Option

Code Controls
A07 Hand-Off-Auto, Speed Potentiometer[10]
B07 Hand-Off-Auto, Start-Stop,
Speed Potentiometer[10]
C07 Start-Stop, Speed Potentiometer[11]
N07 None
N
otes
1. Includes AFC-Off-Bypass switch and Test-Normal switch.
2. Line reactor (A09) is an option for 1 to 20 hp @ 460 V and 1 to 10 hp @ 208/230 V. Line
reactor (A09) is included with 25 to 100 hp @ 460 V and 15 to 50 hp @ 208/230 V.
3. Line contactor (B09) is not compatible with Power Circuit W (Without Bypass).
4. 3 to 15 PSI Transducer (C09) is not compatible with control option C07 (Start-Stop, Speed
Potentiometer), H09 (Analog Card), or J09 (0 to 10 V Auto Speed Reference).
5. Smoke purge E09 permits the motor to run at full speed.
6. Analog card H09 is not compatible with 3 to 15 PSI Transducer (C09).
7. Light Cluster A08, B08, and C08 cannot be selected together; select only one.
8. Light Cluster B08 is not compatible with Power Circuit W (Without Bypass).
9. Light Cluster C08 is not compatible with control option A07 (Hand-Off-Auto, Speed
Potentiometer) or control option B07 (Hand-Off-Auto, Start-Stop, Speed Potentiometer).
10. Hand-Off-Auto switch with Off position for AFC fault reset.
11. Control option C07 (Start-Stop, Speed Potentiometer) is not compatible with Power Circuit
Y (Bypass) or light cluster A08 or B08.
12. Omit the Keypad D09, user must buy a keypad as a separate device to program the
controller.
13. 0-10 V Auto speed reference J09 is not compatible with 3 to 15 PSI Transducer (C09).